TR640IP
12760-0702-00
Page
8 / 18
www.ziehl.de
9.4 Wire line adjustment
To compensate the line resistance short circuit the wires nearby the sensor, measure resistance and enter
this value for line resistance. With 2-wire connection and a common line for all signals, all sensor measuring
currents will be added on the common line. Thus the value of the compensation line resistance RK must be
calculated as follows:
RK = (n+1) x RL/2 (RL = resistance of two wires, n = number of sensors)
10
Operation
10.1 Program selection
Depending on the application, a program with the appropriate default settings can be loaded on the TR640IP.
Settings procedure on the device:
push button down >2s -> programs -> select application area -> select
program.
Setting procedure via web browser:
page “configuration” -> select suitable program from dropdown menu ->
by clicking on “save” the selected program is loaded
.
Pr
Description
sensors
alarms
1.00 Trafo save
3x Pt100
same settings as Pr1 TR250
1T = Pt100
2T = Pt100
3T = Pt100
4T = off
5T = off
6T = off
K1 = fan with cyclic test
K2 = pre-alarm
K3 = tripping
K4 = sensor-/ device error
1.01 Trafo save
1x Pt100, 2x PTC
same settings as Pr3 TR250
1T = Pt100
2T = PTC
3T = PTC
4T = off
5T = off
6T = off
K1 = fan with cyclic test
K2 = pre-alarm
K3 = tripping
K4 = sensor-/ device error
1.02 Trafo save
3x Pt100
same settings as Pr4 TR250
1T = Pt100
2T = Pt100
3T = Pt100
4T = off
5T = off
6T = off
K1 = Sensor 1T
K2 = Sensor 2T
K3 = Sensor 3T
K4 = device error
1.03 Trafo save
4x Pt100
1T = Pt100
2T = Pt100
3T = Pt100
4T = Pt100
5T = off
6T = off
K1 = fan with cyclic test
K2 = pre-alarm + error
K3 = tripping winding
K4 = tripping core
1.04 Trafo save
4x Pt100
1T = Pt100
2T = Pt100
3T = Pt100
4T = Pt100
5T = off
6T = off
K1 = core
K2 = pre-alarm
K3 = tripping winding
K4 = sensor-/ device error
1.05 Trafo save
4x PTC
1T = PTC
2T = PTC
3T = PTC
4T = PTC
5T = off
6T = off
K1 = fan with cyclic test
K2 = pre-alarm + error
K3 = tripping winding
K4 = tripping core
1.06 Trafo save
3x PTC
1T = PTC
2T = PTC
3T = PTC
4T = off
5T = off
6T = off
K1 = pre-alarm
K2 = tripping winding
K3 = tripping core
K4 = sensor-/ device error