10.3 Code lock / code reset
The device can be protected with the code lock against unauthorized changes to the device (via joystick
button) (
menu -> settings -> code lock
). A pin code is used for this (
factory setting: 504
).
Reset pin code / disable code lock,
On the device:
•
Switch off the supply voltage
•
Push the joystick button up (and keep it pressed)
•
Switch on the supply voltage (keep the button pressed)
•
After approx. 4s, the reset menu appears, select the code lock and push the button to the
right
•
Code lock is off, pin code is reset to = 504
Via web interface:
•
Open the page system, deactivate code lock and save it with a push on the save button.
Time on
Duration for which the test is active
00:01 … 23:59
hh:mm
Network
DHCP
Dynamic Host Configuration Protocol
(DHCP)
The device gets its IP address from the
server
on,
off
IP-address
Manual setting of the IP address in the
network
Subnet mask
Manual setting of the subnet mask
Settings
Language
Setting of the language of the display
German,
English
Date
Setting the current date
time
Setting the current time
Display interval
Duration to update the display
0,1 … 2,0 s
Brightness
Display brightness
20 … 100%
Dimming time
Duration until the display brightness is
reduced
00:10 … 59:59
mm:ss
Factory settings
Load the parameters of the current active
program
no,
yes
Code protection
Code protection so that the settings can
be protected
Factory setting: 504
on,
off
Simulation
Sensors
Simulation of a single sensor value
Relay
Simulation of a single relay state
Info
Firmware version
Display of the current installed firmware
version
Serial number
Display the serial number
Operating hours
Operating hours of the device
Comment
Comment of the customer (setting via web
browser only)
Counter
alarm counter
Alarm counter for each alarm
last 20 alarms
statistic 1
Sensor statistic (resettable)
statistic complete
Sensor statistic (not resettable)
reset
Deleting the alarm counter and sensor
statistic 1