SW32V
11820-0701-01
Page
17 / 22
www.ziehl.de
•
Press Down key
Display
8
a1 .
8
•
Press the Set key
Display
8
asy. /
8
off
8
(Asymmetry / Status) flash alternately
•
Set the desired limit or switch off the monitoring with the Up and Down keys
•
Press the Set key
Display
8
dal. /
8
0.10
8
(Delay alarm / Time) flash alternately
•
Set the desired time using the Up and Down keys
•
Press the Set key
Display
8
phf.
8
/
8
off
(Phase sequence / Status) flash alternately
•
Switch monitoring on or off with the Up and Down keys
•
Press the Set key
Display
8
rel /
8
r
(Relay / Parameter) flash alternately
•
Set the desired parameter using the Up and Down keys
•
Press the Set key
Display
8
al 1.
8
•
Repeat configuration for Alarm 2
Configure Delay Display, Display Time
Adjustment process:
•
Select the menu item with the Up/Down key until …
Display
8
ddi.
(Delay display)
•
Press the Set key
Display
8
ddi
8
/
8
0.5
(Delay display / Actual time) flash alternately
•
Set the desired time using the Up and Down keys
•
Press the Set key
Display
8
dit.
(Display time)
•
Set the desired time using the Up and Down keys
•
Press the Set key
Display
8
ddi.
(Delay display)
Simulation
You can simulate a measurement and test the setting here. All 3 phases are simulated simultaneously. All
device functions operate as if this value is actually being measured. Alarm and error messages are only
indicated with the LEDs and not in the display.
The set values are simulated until the menu item
si .
is exited with the Up or Down key. If the SW32V
is locked, simulation is not possible.