SW32V
11820-0701-01
Page
15 / 22
www.ziehl.de
Display mode (last decimal point off)
In the display mode, the SW32V is in its normal state; the current voltages are displayed here. In addition,
the alarm messages (e.g.
8
a1
8
,
8
a2L
8
, …) and error codes (e.g.
8
er9
8
) are displayed.
Function key
Set / Reset
Press briefly: Switches over the measurements, after the last
measurement value
8
Scn
8
mode (measurements are cyclically
displayed until Set is pressed briefly)
Press for > 2 s: Resets after locked alarm
(not possible if DoF Reset delay is counting down)
Press for > 4 s: Displays the program, e.g.
8
Pr1
8
Press for > 10 s: Displays the software version e.g.
8
0-5
8
Function key
Up / Down
Press briefly: Changes into the menus mode
Press for ≥2 s: Displays MAX and MIN measurements,
additionally pressing the Set key for ≥ 2 s deletes the saved values
Menu mode (last decimal point on)
The menu mode is used to select the menu items. If no key is pressed for 30 s, one automatically returns
to the display mode.
Function key
Set / Reset
Press briefly: Changes into the configuration mode
Press for ≥2 s: Returns to the display mode (the most recently set
values are then applied)
Function key
Up / Down
Press briefly: Selects menu item; switches to the
display mode
Configuration mode
(last decimal point flashes)
The value of a parameter can be set in the configuration mode. The display continually alternates between
the parameter name and the currently set value until the Up/Down key is pressed, which changes the
value of the parameter. If no key is pressed for 2 s, the display starts alternating again.
If no key is pressed for 30 s (simulation mode 15 min), one automatically returns to the display mode (the
most recently set value is applied during this)
Function key
Set / Reset
Press briefly: The settings are applied; continues to
next parameter. After the last
parameter, change into menu mode
Press
for ≥2 s: Returns to the display mode (the most recently set
values are then applied)
Function key
Up / Down
Press short/long: Changes the parameter value
(fast/slow)
Hint: Pressing the Up and Down keys simultaneously sets the adjustable value to zero. If you keep the Up
or Down key pressed while setting a value, the speed of the change in the display is accelerated.