Quick Guide SPI1021

 

updated: 2019-09-30 / sm 

from Firmware: 0-0

 

 

SPI1021 

12570-0751-08 

Page

 

1 / 8 

www.ziehl.de 

- Grid- and Plant Protection According to CEI 0-21 and DEWA standard  

 

- with self-test for < 11kW and Watchdog 
- with integrated vector shift relay 
- for plants with possible asymmetry 

≥ 6kVA, power balance has to be monitored extra 

- Pr3 = default 

 

Detailed operating manual see: 

http://www.ziehl.com/en/AllProducts/detail/SPI1021-55

 

 

 

Display and controls 

 
 
 
 
 
 
 
 
 
 
 
 

Test Button 

 

press briefly  

the self-test result is displayed, display next result 

 

Press for > 2 s 

Start self-test, K1 de-energize, K2 energize 

LEDs Inputs status 

(yellow)

 

 

OFF 

Input not active (open) 

ON 

Input active (closed) 

LEDs relay status 

(yellow)

 

 

OFF 

Relay is released 

 

ON 

Relay is operating 

Digital display 4-digits 

(red)

 

 

Depending on program, display of current voltage, frequency, vector shift, average value 

 

Displays the alarm signals, e.g. 

8

AL  

8

8

aL M

8

 

 

Displays the errors with error code e.g. 

8

Err9

8

 

LED Time 

(yellow)

 

 

ON 

A time is displayed 

Last decimal point 

(red)

 

 

OFF 

Display mode 

 

Illuminated 

Menu mode 

 

Flashes 

Configuration mode 

Set / Reset key   

(in display mode, normal state)

 

 

Press briefly 

Display of next measured value / alarm counter 

 

Press for > 2 s 

Reset, quit error messages 

 

Press for > 4 s 

Displays the program, e.g. 

8

Pr 1

8

 

 

Press for > 10 s 

Displays the software version, e.g. 

8

0-0 

8

 

Up / Down key 

 

(in display mode, normal state)

 

 

Press briefly 

Change to the menu mode, display of alarm memory (Down) / cumulative 
time of alarms, standby counter, standby time (Up), pushing Set button for ≥ 
2 s resets the stored values  

 

Press for > 2 s 

Display of MAX (Up) / MIN (Down) - measured values, additional pushing of 
Set button for ≥ 2 s deletes the stored values 

 

 

Summary of Contents for SPI1021

Page 1: ...s status yellow OFF Input not active open ON Input active closed 3 LEDs relay status yellow OFF Relay is released ON Relay is operating 4 Digital display 4 digits red Depending on program display of current voltage frequency vector shift average value Displays the alarm signals e g 8AL 8 8aL M8 Displays the errors with error code e g 8Err98 5 LED Time yellow ON A time is displayed 6 Last decimal p...

Page 2: ...Input volt free contact 8vsr 8 8 off 8 no function 8vsr 8 8 on 8 E1 E2 closed Vector shift active but not evaluated monitoring of feedback contacts off for use with generator mains synchronization Y0 Y1 Inputs feedback contacts Volt free n o or n c contact self learning when switching on Set value turn on time section switch under 8rel 8 8trel 8 can switch off if not connected or if external devic...

Page 3: ...8 110 HM Hysteresis V 10 0 17 5 10 0 10 0 17 5 4 3 dal Response time s 3 00 3 00 3 00 3 00 3 00 3 00 dof OFF delay s 0 0 0 0 0 0 U_ 27 S1 27 S1 u_ Alarm on off On On On On On On u_ Undervoltage V 196 339 196 196 339 85 H_ Hysteresis V 8 0 13 5 8 0 8 0 13 5 3 5 dal Response time s 1 50 1 50 1 50 0 40 0 40 1 50 dof OFF delay s 0 0 0 0 0 0 U__ 27 S2 27 S2 u__ Alarm on off On On On On On On u__ Underv...

Page 4: ...2 vsr Number of phases 3ph 3ph 3ph 3ph 3ph Rocf 81r rocf Alarm on off Off Off Off Off Off Off dfdt delta f delta t Hz s 0 800 0 800 0 800 2 000 2 000 2 000 Per periods 20 20 20 20 20 20 dal Response time s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 1 1 1 rEL trEL response time Y1 s 5 0 5 0 Off 5 0 5 0 5 0 Don Delay On s 300 300 300 300 300 300 Mode mode Mode tran tran tran tran tran tr...

Page 5: ...t 6A WARNING Hazards electrical voltage Can lead to an electric shock and burns Disconnect and de energize before working on the system and the device Comply with the maximum permissible temperature when installing in a switch cabinet Ensure sufficient clearance to other devices or heat sources If cooling is inhibited e g through close proximity to devices with increased surface temperature or int...

Page 6: ... Only change the parameters after having selected the correct program Putting into operation 8 1 Self test execute In programs 1 3 4 the SPI1021 has an automatic self test as recommended in CEI 0 21 and DEWA K1 can pick up only after the self test has been passed once Self test starts automatically as soon as measuring voltage is connected for the first time to a new device and when there is no al...

Page 7: ...own simultaneously sets the value to the lowest value Code Reset 2 s Set when mains are switched on Pin 504 Error messages Err5 Internal control Err7 Contactor feedback contacts K1 Err8 Limit error Err9 Parameter error 1 1 3AC N 300V Menu mode Display mode Configuration mode ...

Page 8: ...ot connected Check for correct connection Set turn on time of section switch under 8trel 8 Do a reset interrupt control voltage for 5s 8Err78 LED K1 flashes und K2 is operating Error when off the section switch Check the connection Check for broken section switch Do a reset interrupt control voltage for 5s 8Err88 appears in the display Hysteresis error Upper threshold value must be higher than the...