SPI1021
12570-0751-08
Seite
8 / 8
www.ziehl.de
Technical Data
Control voltage Us:
Rated-Connection
AC/DC 24-270 V, 0/40...70 Hz, <1,8W / <6,5 VA
DC: 20,4...297 V, AC: 20,4...297 V
Voltage drop
SPI1021 must be supplied with a UPS (>5s)
Output relay:
2 x change-over contact
Switching voltage
Max. AC 440 V
Conventional thermal current Ith
6 A
Inrush current (at 10 % ED)
25 A max. 4 s / 50 A max. 1 s
Nominal operating current Ie (AC 15)
6 A AC 250 V
Recommended series fuse
gG/gL/B 6 A
We reserve the right to make technical changes
Troubleshooting and measures
Error
Cause
Remedy
8
fail
8
as self-test result
Self-test failed
Check all measured voltages
8
EEEE
8
or
8
-EEE
8
appears in the display
Measurement is above/below
range
Measured voltage, frequency or the
vector surge is too large or too small;
comply with measurement range
8
Err5
8
appears in the
display
Error internal interface
Reset
→
interrupt control voltage for
>5s
8
Err7
8
also appears in
the display after 2
automatic reconnection
attempts, LED K1 flashes,
K2 is released
Error when off the section switch,
section switch connected wrong,
faulty or
operated from a third
party switch
Feedback contacts not connected
Set -
8
rel .
8
→
8
trel.
8
→
8
off
8
Feedback contacts not connected
- Check for correct connection
- Set turn-on time of section switch
under
8
trel.
8
- Do a reset
→
interrupt control voltage
for >5s
8
Err7
8
LED K1 flashes
und K2 is operating
Error when off the section switch
- Check the connection
- Check for broken section switch
- Do a reset
→
interrupt control voltage
for >5s
8
Err8
8
appears in the
display
Hysteresis error
Upper threshold value must be higher
than the lower threshold value, check
the threshold values
8
Err9
8
appears in the
display
Parameter error
Reset to factory settings, see “Program
setup”
A time expires in the
display
Always when an OFF-delay time
8
dof
8
is running, it is counted
down in the display (shortest one
first)
Wait until the time has expired
(depending on the setting, several
times may elapse one after the other)
Device cannot be
configured / only the limits
can be configured
Code lock / Sealing activated
If there are any problems with the code
lock (pin forgotten), the lock can be
switched off and the pin can be reset
to 504 by keeping the Set key pressed
while switching on the mains until
8
Code
8
/ off
8
appears in the display.
Implausible voltage values
Pr selected with N, but N not
connected
Select Pr without N or connect N
8
Loc
8
appears in the
display
Seal is active
See Sealing
8
Code
8
appears in the
display
Code lock is active
See „Code lock“
8
stby
8
appears in the
display
Standby mode, E1-E2 closed
Check parameter
8
vsr.
8