Default settings and firmware version 

When changing programs, all parameters are reset to the *default settings. 

Menu 

item 

Parameter / Unit 

Default setting 

Users 

data 

CEI 0-21 

DEWA 

3AC+N 

230V 

3AC 

400V 

1AC+N 

230V 

3AC+N 

230V 

3AC 

400V 

3AC 

100V 

 

Pr1

 

Pr2

 

Pr3 

*

 

Pr4

 

Pr5

 

Pr6

 

 

U,, 

59.S2 

59>S2

 

u,,

 

Alarm on/off 

 

Off 

Off 

Off 

Off 

Off 

OFF 

 

u,,

 

Overvoltage

 

264 

458 

264 

264 

458 

115 

 

H,,

 

Hysteresis 

10.5 

17.5 

10.5 

10.5 

17.5 

4.5 

 

dal

 

Response time 

0.10 

0.10 

0.10 

0.10 

0.10 

0.10 

 

dof

 

OFF-delay

 

s

 

 

U, 

59.S1 

59>S1

 

u,

 

Alarm on/off 

 

On 

On 

On 

On 

On 

On 

 

u,

 

Overvoltage

 

264 

458 

264 

253 

438 

120 

 

H,

 

Hysteresis 

10.5 

17.5 

10.5 

10.5 

17.5 

4.3 

 

dal

 

Response time

 

s

 

0.20 

0.20 

0.20 

0.20 

0.20 

0.60 

 

dof

 

OFF-delay

 

s

 

 

UM 

59-Av

 

UM

 

Alarm on/off 

 

On 

On 

On 

On 

On 

Off 

 

UM

 

Overvoltage

 

253 

438 

253 

253 

438 

110 

 

HM

 

Hysteresis 

10.0 

17.5 

10.0 

10.0 

17.5 

4.3 

 

dal

 

Response time

 

3.00 

3.00 

3.00 

3.00 

3.00 

3.00 

 

dof

 

OFF-delay

 

 

U_ 

27.S1 

27<S1

 

u_

 

Alarm on/off 

 

On 

On 

On 

On 

On 

On 

 

u_

 

Undervoltage

 

196 

339 

196 

196 

339 

85 

 

H_

 

Hysteresis 

8.0 

13.5 

8.0 

8.0 

13.5 

3.5 

 

dal

 

Response time

 

1.50 

1.50 

1.50 

0.40 

0.40 

1.50 

 

dof

 

OFF-delay

 

s

 

 

U__ 

27.S2 

27<S2

 

u__

 

Alarm on/off 

 

On 

On 

On 

On 

On 

On 

 

u__

 

Undervoltage

 

34.5 

60 

34.5 

92 

159 

3.0 

 

H__

 

Hysteresis

 

3.7 

3.7 

3.7 

3.7 

6.4 

1.5 

 

dal

 

Response time

 

0.20 

0.20 

0.20 

0.20 

0.20 

0.20 

 

dof

 

OFF-delay

 

 

F,, 

81.S2 

81>S2

 

F,,

 

Alarm on/off 

 

On 

On 

On 

On 

On 

On 

 

F,,

 

Overfrequency

 

Hz 

51.50 

51.50 

51.50 

54.00 

54.00 

54.00 

 

H,,

 

Hysteresis

 

Hz 

0.10 

0.10 

0.10 

0.10 

0.10 

0.10 

 

dal

 

Response time

 

0.10 

0.10 

0.10 

10.0 

10.0 

10.0 

 

dof

 

OFF-delay

 

s

 

 

F, 

81.S1 

81>S1

 

F,

 

Alarm on/off 

 

Off 

Off 

Off 

Off 

Off 

Off 

 

F,

 

Overfrequency

 

Hz 

50.20 

50.20 

50.20 

52.50 

52.50 

52.50 

 

H,

 

Hysteresis

 

Hz 

0.10 

0.10 

0.10 

0.10 

0.10 

0.10 

 

dal

 

Response time

 

0.10 

0.10 

0.10 

0.10 

0.10 

0.10 

 

dof

 

OFF-delay

 

 

 

 

Summary of Contents for SPI1021

Page 1: ...s status yellow OFF Input not active open ON Input active closed 3 LEDs relay status yellow OFF Relay is released ON Relay is operating 4 Digital display 4 digits red Depending on program display of current voltage frequency vector shift average value Displays the alarm signals e g 8AL 8 8aL M8 Displays the errors with error code e g 8Err98 5 LED Time yellow ON A time is displayed 6 Last decimal p...

Page 2: ...Input volt free contact 8vsr 8 8 off 8 no function 8vsr 8 8 on 8 E1 E2 closed Vector shift active but not evaluated monitoring of feedback contacts off for use with generator mains synchronization Y0 Y1 Inputs feedback contacts Volt free n o or n c contact self learning when switching on Set value turn on time section switch under 8rel 8 8trel 8 can switch off if not connected or if external devic...

Page 3: ...8 110 HM Hysteresis V 10 0 17 5 10 0 10 0 17 5 4 3 dal Response time s 3 00 3 00 3 00 3 00 3 00 3 00 dof OFF delay s 0 0 0 0 0 0 U_ 27 S1 27 S1 u_ Alarm on off On On On On On On u_ Undervoltage V 196 339 196 196 339 85 H_ Hysteresis V 8 0 13 5 8 0 8 0 13 5 3 5 dal Response time s 1 50 1 50 1 50 0 40 0 40 1 50 dof OFF delay s 0 0 0 0 0 0 U__ 27 S2 27 S2 u__ Alarm on off On On On On On On u__ Underv...

Page 4: ...2 vsr Number of phases 3ph 3ph 3ph 3ph 3ph Rocf 81r rocf Alarm on off Off Off Off Off Off Off dfdt delta f delta t Hz s 0 800 0 800 0 800 2 000 2 000 2 000 Per periods 20 20 20 20 20 20 dal Response time s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 1 1 1 rEL trEL response time Y1 s 5 0 5 0 Off 5 0 5 0 5 0 Don Delay On s 300 300 300 300 300 300 Mode mode Mode tran tran tran tran tran tr...

Page 5: ...t 6A WARNING Hazards electrical voltage Can lead to an electric shock and burns Disconnect and de energize before working on the system and the device Comply with the maximum permissible temperature when installing in a switch cabinet Ensure sufficient clearance to other devices or heat sources If cooling is inhibited e g through close proximity to devices with increased surface temperature or int...

Page 6: ... Only change the parameters after having selected the correct program Putting into operation 8 1 Self test execute In programs 1 3 4 the SPI1021 has an automatic self test as recommended in CEI 0 21 and DEWA K1 can pick up only after the self test has been passed once Self test starts automatically as soon as measuring voltage is connected for the first time to a new device and when there is no al...

Page 7: ...own simultaneously sets the value to the lowest value Code Reset 2 s Set when mains are switched on Pin 504 Error messages Err5 Internal control Err7 Contactor feedback contacts K1 Err8 Limit error Err9 Parameter error 1 1 3AC N 300V Menu mode Display mode Configuration mode ...

Page 8: ...ot connected Check for correct connection Set turn on time of section switch under 8trel 8 Do a reset interrupt control voltage for 5s 8Err78 LED K1 flashes und K2 is operating Error when off the section switch Check the connection Check for broken section switch Do a reset interrupt control voltage for 5s 8Err88 appears in the display Hysteresis error Upper threshold value must be higher than the...

Reviews: