background image

datum / name ) :  27.01.05 Fz 

Z. Nr.: 1173 0750 

Page  5  von  6 

Type: TR 111 V 

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]

 

Technical data 

Power Supply 

(version see lateral type plate) 

  Supply Voltage Us 

AC 230 V 

50/60 Hz 

   

AC 24 V / DC 20...30 V without potentially separation 

  Tolerance Voltage Us 

AC : +10 % / -15 % 

  Frequency (AC) 

48...62 Hz 

  Power Consumption 

< 3 VA 

Sensor connection 

Pt 100  EN 60751 

  Sensor voltage 

<5 V 

  Sensor current 

<3 mA 

  Short circuit 

<15 Ω 

Limit value 
  Measuring- ranges 

3 or 4 ranges switchable 

 

3 measuring-ranges 

-10...40 °C / 0...100°C / 0...200°C 

 

  Repead error 

app. 0,5 K 

 

4 measuring-ranges 

0...100°C / 100...200°C / 200...300°C / 300...400°C 

 

  Repead error 

app. 0,8 K 

 

Error of setting 

±5 K 

 

Temperature-dependence 

≤0,05 %/K 

 

Hysteresis 

adjustable app. 2...10 K 

 

Switching delay don/doff 

adjustable 0,1 s...10 s 

Relay output 

1 change-over contact (co) 

  Switching voltage 

max. AC 250 V 

  Switching current 

max. 5 A 

  Switching power AC cos 

= 1 

max. 1250 VA (ohmic load) 

   

max. 48 W at DC 24 V 

  Derating factor at cos 

 0,7 

0,5 

  Rated operational current AC 15 

Ie = 2  A 

Ue = 250 V 

  Rated operational current DC 13 

Ie = 2  A 

Ue = 24 V 

   

Ie = 0,2  A 

Ue = 125 V 

   

Ie = 0,1  A 

Ue = 250 V 

  Recommended Fuse 

3,15 A gl (slow) 

  Mechanical Contact Life 

1 x 10

7

 operations 

  Electrical Contact Life 

1 x 10

5

 operations at AC 250 V 5 A 

   

2 x 10

5

 operations at AC 250 V 3 A 

   

6 x 10

5

 operations at AC 250 V 1 A 

Testing conditions 

EN 50178 / EN 60947 

  Rated insulation voltage Ui 

AC 250 V 

  Insulation 

EN 60664 

  Contamination Level 

  Rated impulse voltage 

4000 V 

  Transformer 

EN 61558 

  EMC 

EN 50081-2/EN 50082-2 

  On period 

100 % 

  max. ambient temperature 

-20 °C... +55 °C 

 

Summary of Contents for Pt 100

Page 1: ...o KG Daimlerstr 13 D 74523 Schwäbisch Hall Tel 49 791 504 0 Fax 56 e mail info ziehl de Operating manual Pt 100 Temperature Relay TR 111 V MINIPAN digital panel meters temperature and mains controlling special purpose instruments for customer requirements www ziehl com Archive document www ziehl de ...

Page 2: ...erature in processes plants and machines Monitoring of temperatures in bearings Controlling of temperatures in processes and plants Overview of functions Measuring input 1x Pt 100 RTD 2 wire 3 or 4 measuring ranges switchable 1 limit adjustable 0 100 switching delay adjustable 0 1 10 s Output relay 1 changeover contact co Operating or closed current tprinciple selectable with bridge Switching off ...

Page 3: ...ple If a temperature sensor is connected the installed relay picks up 11 14 closed ok The relay releases in the case of a sensor breakdown The thermostat signals and switches when the set limit is exceeded If the temperature at the sensor rises over the adjusted value then the relay releases The switching status is signalled by a LED relay picked up LED on At operating current principle the functi...

Page 4: ...ructions may lead to death physical injury or damage of the equipment itself and of other apparatus and equipment If in any case the information in the instructions manual is not sufficient please contact our company or the responsible representative Instead of the industrial norms and regulations written in this instructions manual valid for Europe you must observe out of their geographical scope...

Page 5: ...Error of setting 5 K Temperature dependence 0 05 K Hysteresis adjustable app 2 10 K Switching delay don doff adjustable 0 1 s 10 s Relay output 1 change over contact co Switching voltage max AC 250 V Switching current max 5 A Switching power AC cos 1 max 1250 VA ohmic load max 48 W at DC 24 V Derating factor at cos 0 7 0 5 Rated operational current AC 15 Ie 2 A Ue 250 V Rated operational current D...

Page 6: ...ted ferrules 1 x 2 5 mm2 Protection class housing IP 30 Protection class terminals IP 20 Attachment Mounting 35 mm standard rail according to EN 60715 Optional Screw mounting M4 Weight approx 130 g Subject to technical modifications Form V2 Dimensions in mm 1 Oberteil cover 2 Unterteil base 3 Riegel bar for snap mounting 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzei...

Reviews: