background image

 

MU100W 

12100-0703-00

 

Page

 

5 / 6 

www.ziehl.de 

  

Technical data 

Rated supply voltage Us (A1, A2) 

DC/AC 24 

– 240 V  0/50/60 Hz 

Tolerance 

DC 20.4 - 297 V   

AC 20 - 264 V 

Power consumption 

< 3 W 

< 5 VA 

 

Measuring input (+, In, GND) 

 

Resistance potentiometer 

0…500 Ω bis 0…10 kΩ 

Measuring current/-voltage 

6,6 mA…330 µA / 3,3 V 

Measuring cycle / measuring time 

< 15 ms 

 

Analog output (GND, U, I) 

Not electrically isolated from the potentiometer 

Voltage output 0…10 V 

min. 1 kΩ accuracy 0,3 % of Full-scale 

Temperature drift 

< 0,01 %/K 

 

 

Current output 0/4…20 mA 

max. 500 Ω accuracy 0,3 % of Full-scale 

Temperature drift 

< 0,015 %/K 

Fault burden 

(250 Ω - burden)/250 Ω * 0,3 % of the current 

 
For parameter error Full-scale approx. 22mA / 12V are output. 
For parameter error zero approx. 0mA / 0V are output. 
 

Test conditions 

EN 61010-1 

Rated impulse voltage 

4000 V 

Overvoltage category 

II reinforced insulation 

Pollution degree 

Rated insulation voltage Ui 

250 V 

On-period 

100 % 

 

EMC-tests 

 

Emission 

EN 61000-6-3 

Immunity 

EN 61000-6-2 

 

Installation conditions 

 

Permissible ambient temperature 

-20 °C ... +60 °C 

Permissible storage temperature 

-

20 °C …+70 °C 

Installation height 

< 2000 m over N.N. 

Climatic conditions 

5 - 85% rel. humidity, no condensation 

Permissible wiring temperature 

-

5 °C …+70 °C 

Vibration resistance EN 60068-2-6 

2…25 Hz ±1,6 mm 

 

25 ... 150 Hz 5 g 

 

Housing 

Design V2 

Dimension (H x W x D) 

90 x 35 x 58 mm 

Plastic material 

PA66 

Fire protection class 

UL94V-2 

Connection terminal 

 

Line connection solid wire 

1 x 0,34 - 1,5 mm² / AWG 22 - 14 

Standard wire with insulated ferrules 

1 x 0,1 - 1,0 mm² / AWG 27 - 16 

Insulation strip length min. / Tightening torque 

8 mm / 0,5 Nm 

Protection class housing / terminals 

IP 40 / IP20 

Mounting EN60715 

Standard rail 35 mm 

Optional: screw mounting 

M4, only with additional bolt (not part of delivery) 

Weight 

approx. 130 g 

 

Subject to technical modifications 

Summary of Contents for MU100W

Page 1: ...iehl de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual MU100W updated 2018 11 09 sm MU100W 12100 0703 00 Page 1 6 www ziehl de Measuring Transducer for Potentiometers ...

Page 2: ...7 4 Current voltage output 4 7 5 Factory setting 4 8 Technical data 5 9 Housing Type V2 6 1 Display and controls 2 Application and short description The MU100W measuring transducer converts the position of a potentiometer into a linear signal 0 4 20 mA respectively 0 10 V Zero can be easily scaled 0 40 Full scale 60 100 of the range of the potentiometers by pressing a button The built in universal...

Page 3: ...close proximity of apparatus with elevated surface temperature or hindrance of the cooling air the tolerable environmental temperature is diminishing To use the equipment flawless and safe transport and store properly install and start professionally and operate as directed Only let persons work with the equipment who are familiar with installation start and use and who have appropriate qualificat...

Page 4: ...arameterization mode press the button Zero for 10s when applying the control voltage until the power LED starts to flash To exit parameterization mode prematurely press the Full scale and zero buttons at the same time The parameterization mode is automatically exited after 10 minutes The set values remain stored even when the control voltage is switched off 7 2 Adjustment zero point 0 40 of the ad...

Page 5: ...00 V Overvoltage category II reinforced insulation Pollution degree 2 Rated insulation voltage Ui 250 V On period 100 EMC tests Emission EN 61000 6 3 Immunity EN 61000 6 2 Installation conditions Permissible ambient temperature 20 C 60 C Permissible storage temperature 20 C 70 C Installation height 2000 m over N N Climatic conditions 5 85 rel humidity no condensation Permissible wiring temperature...

Page 6: ...l base 3 Riegel bar for snap mounting 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung Ø 4 2 mm for fixing to wall with screws Ø 4 2 48 58 45 3 61 8 16 5 90 Option 98 116 35 3 4 1 2 5 7 6 ...