MU100W
12100-0703-00
Page
5 / 6
www.ziehl.de
8
Technical data
Rated supply voltage Us (A1, A2)
DC/AC 24
– 240 V 0/50/60 Hz
Tolerance
DC 20.4 - 297 V
AC 20 - 264 V
Power consumption
< 3 W
< 5 VA
Measuring input (+, In, GND)
Resistance potentiometer
0…500 Ω bis 0…10 kΩ
Measuring current/-voltage
6,6 mA…330 µA / 3,3 V
Measuring cycle / measuring time
< 15 ms
Analog output (GND, U, I)
Not electrically isolated from the potentiometer
Voltage output 0…10 V
min. 1 kΩ accuracy 0,3 % of Full-scale
Temperature drift
< 0,01 %/K
Current output 0/4…20 mA
max. 500 Ω accuracy 0,3 % of Full-scale
Temperature drift
< 0,015 %/K
Fault burden
(250 Ω - burden)/250 Ω * 0,3 % of the current
For parameter error Full-scale approx. 22mA / 12V are output.
For parameter error zero approx. 0mA / 0V are output.
Test conditions
EN 61010-1
Rated impulse voltage
4000 V
Overvoltage category
II reinforced insulation
Pollution degree
2
Rated insulation voltage Ui
250 V
On-period
100 %
EMC-tests
Emission
EN 61000-6-3
Immunity
EN 61000-6-2
Installation conditions
Permissible ambient temperature
-20 °C ... +60 °C
Permissible storage temperature
-
20 °C …+70 °C
Installation height
< 2000 m over N.N.
Climatic conditions
5 - 85% rel. humidity, no condensation
Permissible wiring temperature
-
5 °C …+70 °C
Vibration resistance EN 60068-2-6
2…25 Hz ±1,6 mm
25 ... 150 Hz 5 g
Housing
Design V2
Dimension (H x W x D)
90 x 35 x 58 mm
Plastic material
PA66
Fire protection class
UL94V-2
Connection terminal
Line connection solid wire
1 x 0,34 - 1,5 mm² / AWG 22 - 14
Standard wire with insulated ferrules
1 x 0,1 - 1,0 mm² / AWG 27 - 16
Insulation strip length min. / Tightening torque
8 mm / 0,5 Nm
Protection class housing / terminals
IP 40 / IP20
Mounting EN60715
Standard rail 35 mm
Optional: screw mounting
M4, only with additional bolt (not part of delivery)
Weight
approx. 130 g
Subject to technical modifications