Installation 

The unit can be installed as follows: 

  Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715 for protection against 

fire, external environmental conditions and mechanical effects. 

  With screws M4 for installation on walls or panel. (additional latch is not included in delivery) 

  Connection according to connection plan or type plate. 

 
Failure to comply with the information in this instruction manual will not guarantee the function of the device. 
 

A circuit-breaker or switch must be situated within easy reach of the  
unit and fused. Installation excess current protection should be ≤ 10 A.  
 

 
 

Commissioning 

LED Power is on = device ready for operation 
LED Power flashing = parameterization mode 
LED 4...20 mA flashes 3 times in parameterization mode = value accepted 
LED 4...20 mA flashing = parameterisation error (with 22 mA/12 V Full-scale output outside the setting 
rang, with 0 mA/0 V zero outside the setting range) 
LED 4...20 mA is on = current output 4...20 mA 

 

7.1  Parameter mode (Power LED flashing) 

To enter the parameterization mode, press the button Zero for 10s when applying the control voltage until the 
power LED starts to flash. To exit parameterization mode prematurely, press the Full-scale and zero buttons 
at the same time. The parameterization mode is automatically exited after 10 minutes. The set values remain 
stored even when the control voltage is switched off. 
 

7.2  Adjustment zero point (0 

– 40% of the adjustment range) 

Set the resistance potentiometer to the desired zero point and press the zero button. 
Acceptance of the value is acknowledged by flashing the LED 4…20mA 3 times, otherwise repeat 
adjustment. 
 

7.3  Adjustment Full-scale (60 

– 100% of adjustment range) 

Set the resistance potentiometer to the desired Full-scale and press the Full-scale button. 
Acceptance of the value is acknowledged by flashing the LED 4…20mA 3 times, otherwise repeat 
adjustment. 
 

7.4  Current/ voltage output 

To switch the current output to 4…20 mA, press and hold the Full-scale button for approx. 5s until the yellow 
LED 4…20 mA lights up. 
To switch the current output to 0…20 mA, press and hold the zero button for approx.. 5s until the yellow LED 
4…20 mA goes out. 
The voltage output is always s

et to 0…10 V independent of the current output. 

 

7.5  Factory setting 

The current output is factory set to 0…20 mA. 
 

 

Summary of Contents for MU100W

Page 1: ...iehl de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual MU100W updated 2018 11 09 sm MU100W 12100 0703 00 Page 1 6 www ziehl de Measuring Transducer for Potentiometers ...

Page 2: ...7 4 Current voltage output 4 7 5 Factory setting 4 8 Technical data 5 9 Housing Type V2 6 1 Display and controls 2 Application and short description The MU100W measuring transducer converts the position of a potentiometer into a linear signal 0 4 20 mA respectively 0 10 V Zero can be easily scaled 0 40 Full scale 60 100 of the range of the potentiometers by pressing a button The built in universal...

Page 3: ...close proximity of apparatus with elevated surface temperature or hindrance of the cooling air the tolerable environmental temperature is diminishing To use the equipment flawless and safe transport and store properly install and start professionally and operate as directed Only let persons work with the equipment who are familiar with installation start and use and who have appropriate qualificat...

Page 4: ...arameterization mode press the button Zero for 10s when applying the control voltage until the power LED starts to flash To exit parameterization mode prematurely press the Full scale and zero buttons at the same time The parameterization mode is automatically exited after 10 minutes The set values remain stored even when the control voltage is switched off 7 2 Adjustment zero point 0 40 of the ad...

Page 5: ...00 V Overvoltage category II reinforced insulation Pollution degree 2 Rated insulation voltage Ui 250 V On period 100 EMC tests Emission EN 61000 6 3 Immunity EN 61000 6 2 Installation conditions Permissible ambient temperature 20 C 60 C Permissible storage temperature 20 C 70 C Installation height 2000 m over N N Climatic conditions 5 85 rel humidity no condensation Permissible wiring temperature...

Page 6: ...l base 3 Riegel bar for snap mounting 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung Ø 4 2 mm for fixing to wall with screws Ø 4 2 48 58 45 3 61 8 16 5 90 Option 98 116 35 3 4 1 2 5 7 6 ...

Reviews: