5-19 Terminal 37 Safe Stop
Option:
Function:
[1] *
Safe Stop Alarm
Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital input or
fieldbus.
[3]
Safe Stop Warning
Coasts frequency converter when safe stop is activated (T-37 off). When safe stop circuit is rees-
tablished, the frequency converter will continue without manual reset.
[4]
PTC 1 Alarm
Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital input or
fieldbus. Choice 4 is only available when the MCB 112 PTC Thermistor Card is connected.
[5]
PTC 1 Warning
Coasts frequency converter when safe stop is activated (T-37 off). When safe stop circuit is rees-
tablished, the frequency converter will continue without manual reset, unless a Digital Input set to
PTC Card 1 [80] is still enabled. Choice 5 is only available when the MCB 112 PTC Thermistor Card
is connected.
[6]
PTC 1 & Relay A
This choice is used when the PTC option is gated together with a Stop button through a Safety relay
to T-37. Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital
input or fieldbus. Choice 6 is only available when the MCB 112 PTC Thermistor Card is connected.
[7]
PTC 1 & Relay W
This choice is used when the PTC option is gated together with a Stop button through a Safety relay
to T-37. Coasts frequency converter when safe stop is activated (T-37 off). When safe stop circuit
is reestablished, the frequency converter will continue without manual reset, unless a Digital Input
set to PTC Card 1 [80] is (still) enabled. Choice 7 is only available when the MCB 112 PTC Thermistor
Card is connected.
[8]
PTC 1 & Relay A/W
This choice makes it possible to use a combination of Alarm and Warning. Choice 8 is only available
when the MCB 112 PTC Thermistor Card is connected.
[9]
PTC 1 & Relay W/A
This choice makes it possible to use a combination of Alarm and Warning. Choice 9 is only available
when the MCB 112 PTC Thermistor Card is connected.
Choises 4 - 9 are only available when the MCB 112 PTC Thermistor Card is connected.
NB!
When Auto Reset/ Warning is selected the frequency converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function
No.
PTC
Relay
No Function
[0]
-
-
Safe Stop Alarm
[1]*
-
Safe Stop [A68]
Safe Stop Warning
[3]
-
Safe Stop [W68]
PTC 1 Alarm
[4]
PTC 1 Safe Stop [A71]
-
PTC 1 Warning
[5]
PTC 1 Safe Stop [W71]
-
PTC 1 & Relay A
[6]
PTC 1 Safe Stop [A71]
Safe Stop [A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Stop [W71]
Safe Stop [W68]
PTC 1 & Relay A/W
[8]
PTC 1 Safe Stop [A71]
Safe Stop [W68]
PTC 1 & Relay W/A
[9]
PTC 1 Safe Stop [W71]
Safe Stop [A68]
W means warning and A means alarm. For further information, see Alarms and Warnings in section
Troubleshooting
in the Design Guide or the Operating
Instructions
A dangerous failure related to Safe Stop will give Alarm: Dangerous Failure [A72].
Please refer to the section
Description of Alarm Word, Warning Word and extended Status Word
in the chapter
Troubleshooting
.
5 Parameter Setup
MCB 112 VLT
®
PTC Thermistor Option
18
MG.33.V2.02 - VLT
®
is a registered Danfoss trademark
5
Summary of Contents for MS 220 DA
Page 3: ......
Page 9: ...3 Assembly Motor Protection MS 220 DA 6 MG33V102 VLT is a regisered Danfoss trademark 3 ...
Page 11: ...4 Technical Data Motor Protection MS 220 DA 8 MG33V102 VLT is a regisered Danfoss trademark 4 ...
Page 19: ...7 Certificates Motor Protection MS 220 DA 16 MG33V102 VLT is a regisered Danfoss trademark 7 ...
Page 20: ...Motor Protection MS 220 DA 7 Certificates MG33V102 VLT is a regisered Danfoss trademark 17 7 ...
Page 21: ...7 Certificates Motor Protection MS 220 DA 18 MG33V102 VLT is a regisered Danfoss trademark 7 ...
Page 22: ......
Page 25: ......