background image

 

FR(MU)1000 

12460-0751-02

 

Seite

 

8 / 8 

www.ziehl.de 

  

 

Cable length for proximity switch   

 

PNP, NPN, 2-wire  

 

      

Resistance of line   

≤ 10 Ω / line 

         

Capacity of line 

 

≤ 22 nF 0…800Hz; ≤ 10 nF 800...1600 Hz 

 

      

e.g. max. length of cable    

< 150 m with cable LIFYY11Y 3*0,34 mm 

 

 

 

at 0…800Hz 

 

Measuring error 

 

± 0,05 % of measured value ± 1 Digit 

 

Temperature factor   

< 0,002 %/K 

 

Measuring time 

 

1 Period * 

Svm

 (number mean values) 

 

 

 

>= 3 Periods; after placing the measuring signal 

 

Auxiliary 18 V 20 mA   

16 ... 21 V max. 20 mA 

 

 

Enable E1-E2 

18 V / 3 mA   Switching threshold approx. 9 V 

 

 

Analogue output: (FRMU only) 

 

electrically insulated to input f - in (U1-U2) 

 

Voltage output 0...10 V 

 

max. 10 mA  error <0,1 % of full scale 

 

Temperature factor   

< 0,01 %/K 

 

Current output 0/4...20 mA 

 

max. 500 Ω   error <0,15 % of full scale 

 

Temperature factor   

< 0,015 %/K 

 

Error from burden   

(250 Ω - resistance)/250 Ω * 0,15 % of final value 

 

Nominal rise time 

<20ms + messuring time 

 

Resolution analog output 

>= 11,6 bit 

 

Subject to technical changes

 

 

Type V4 

Dimensions in mm 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Cover 

Base 

Bar for snap mounting 

Latch for sealing 

Front panel 

Position downward 

For fixing to wall with screws, Ø 4,2 mm 

48

58

4

5

3

6

1

,8

16,5

(9

0

)

Option

70

9

8

1

1

6

6

1

2

3

4

5

7

Summary of Contents for FRMU1000

Page 1: ... relay state 5 Pushbutton up 2 Digital display 5 digits 6 Pushbutton set reset 3 LED speed measuring 1 min 7 Pushbutton down 4 LED frequency measuring Hz 2 Presetting 2 programs Pr can be selected Due to these Programs the device can be easily adapted to the application Choose the Program fitting to your application and after that change the parameters When changing the program all parameters are ...

Page 2: ...Z00 H Hysterisis 10 1Z00 dAL Alarm delay 0Z50 0Z10 dof Switch back delay 0Z50 0Z10 rel Relais function r r Alarm 2 AL 2 K2 Limit 2 lower window limit 5000 47Z00 Fvnc Function k alHi upper window limit 53Z00 H Hysterisis 100 1Z00 dAL Alarm delay 0Z50 0Z10 dof Switch back delay 0Z50 0Z10 rel Relais function r r denab Start up delay 2Z0 0Z1 ddisp Display delay 0Z5 0Z5 ovt nur FRMU Type 0 10 0 10 ____...

Page 3: ...d and relevant regulations of the corresponding country Observe the maximum temperature permissible when installing in switching cabinet Make sure sufficient space to other equipment or heat sources If the cooling becomes more difficult e g through close proximity of apparatus with elevated surface temperature or hindrance of the cooling air the tolerable environmental temperature is diminishing A...

Page 4: ...d over frequency without reclosing lock overspeed over frequency with reclosing lock w_r underspeed under frequency without reclosing lock w__ underspeed under frequency with reclosing lock k window monitoring without reclosing lock window monitoring with reclosing lock alhi upper limit when monitoring a window H hysterisis dal switching delay doF switch back delay rEl function of relay r closed c...

Page 5: ...Si o k Pi n Zero Fullscale Svm AL 2 Limit 00005 99999 f vnc of f w _r w __ k al H i 00005 99999 H 00001 10000 dAL 000 05 099 99 s doF 000 05 099 99 s r EL r A denab Value ddi sp Value 00000 99999 00000 09999 00001 00250 di v 00001 00250 m vl t Value Value Value Up Set Down Reset 2s Set 0000 0 0060 0 0000 1 0002 0 s s FRMU only Up down at same time sets values on zero Code reset 2 s set while switc...

Page 6: ...c of f w _r w __ k al H i 010 00 500 00 H 000 10 010 00 dAL 000 05 099 99 s doF 000 05 099 99 s r EL r A 0000 0 0060 0 denab Value 0000 1 0002 0 ddi sp Value 010 00 500 00 00000 09999 Up Set Down Reset 2s Set s s FRMU only 6 3 Program 2 Pr2 Frequency Monitoring Operation with pushbuttons Up down on same time sets values on zero Code reset 2 s set while switching in Pin 00504 error messages Er 9 de...

Page 7: ...40 V Tolerance DC 20 4 297 V AC 20 264 V Frequency 0 40 500 Hz from AC 80 V 10 500 Hz Input 3 W 10 VA Relay output 2 x 1 Changer CO Switching voltage max AC 400 V Switching current max 5 A Switching power max 1250 VA ohm resistive load max 48 W at DC 24 V Nominal operating current Ie AC 15 Ie 2 A Ue 250 V DC 13 Ie 2 A Ue 24 V Ie 0 2 A Ue 240 V Contact life mechanic 15 x 106 Switching cycles Contac...

Page 8: ...e E1 E2 18 V 3 mA Switching threshold approx 9 V Analogue output FRMU only electrically insulated to input f in U1 U2 Voltage output 0 10 V max 10 mA error 0 1 of full scale Temperature factor 0 01 K Current output 0 4 20 mA max 500 Ω error 0 15 of full scale Temperature factor 0 015 K Error from burden 250 Ω resistance 250 Ω 0 15 of final value Nominal rise time 20ms messuring time Resolution ana...