![ZIEHL-ABEGG Ucontrol PXDM Series Manual Download Page 26](http://html.mh-extra.com/html/ziehl-abegg/ucontrol-pxdm-series/ucontrol-pxdm-series_manual_933539026.webp)
Handbook
Ucontrol
type-lines PXDM
Date 06/04
TBL02_55-GB06/04
Part.-No. 00153239-GB
Page 26 / 105
Mode
Function:
Ziehl-Abegg Sensor / Signal
alternative selection Sensor signal
Example of application
4.01
Pressure control for
ventilation systems
1x Pressure DSG../ 0-10 V
0-10 V, 0-20 mA, 4-20 mA
variable air volume systems
(VVS)
Setpoint in Pa
¨
central exhaust on meeting demand over roof
fans by controlling fan speed
¨
air conditioning for buildings by controlling
fan speed in air handling units
4.02
Pressure control for
ventilation systems
setpoint depending
on outdoor
temperature
1x pressure DSG../ 0-10 V
0-10 V, 0-20 mA, 4-20 mA
1x temperatur TF../ KTY10-6
0-10 V, 0-20 mA, 4-20 mA
variable air volume systems
(VVS)
Setpoint in Pa
¨
central exhaust on meeting demand over roof
fans by controlling fan speed ( pressure
setpoint depending on outdoor temperature).
¨
air conditioning for buildings by controlling
fan speed in air handling units. Pressure
setpoint depending on outdoor temperature.
5.01
Volume control
(constant) for
ventilation systems.
For centrifugal fans
by means of a ring
conduit in the inlet
duct (setting K-
factor
)
1x pressure DSG../ 0-10 V
0-10 V, 0-20 mA, 4-20 mA
air conditioning for buildings by controlling fan
speed in air handling units for ventilation systems
Setpoint in m
3
/h
5.02
Volume control
(constant) for
ventilation
systems.Setpoint
depending on
outdoor temperature
1x Pressure DSG../ 0-10 V
0-10 V, 0-20 mA, 4-20 mA
1x temperature TF../ KTY10-6
0-10 V, 0-20 mA, 4-20 mA
air conditioning for buildings by controlling fan
speed in air handling units for ventilation systems
Setpoint in m
3
/h
Air volume setpoint depending on outdoor
temperature.
6.01
Air velocity control
1x Air velocity MAL../ 0-10 V
0-10 V, 0-20 mA, 4-20 mA
Constant air volume for clean rooms with particel
filters by speed control of fan.
Setpoint m/s
A Ziehl-Abegg sensor with the standard signal (KTY, 0-10 V or 4-20 mA) and the corresponding
measuring range is allocated via the selection of the mode of operation.
When using
other sensors
, a corresponding adaptation to the type of signal and the sensor
measuring range can be carried out (
F
the respective mode of operation).
Summary of Contents for Ucontrol PXDM Series
Page 80: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 80 105 ...
Page 92: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 92 105 ...
Page 96: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 96 105 ...
Page 100: ......