Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
passive Sensor type
“
TF..
”
Setting range: 0-120.0 K (Kelvin)
Factory setting: 5.0 K, (at
2.02
: 20.0 K)
active Sensor type
“
MTG-120V
”
Setting range: -10.0...+120.0 K
Factory setting: 65.0 K
Min. Speed
Min. Speed
(basic speed only when needed)
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Factory setting:
|
OFF
|
Max. Speed
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting: 50.0 Hz
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed manual
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Operating Instructions
Icontrol
–
model series FXDM
Programming
L-BAL-E036-GB 2022/47 Index 011
Part.-No.
39/108