Diagram setting signal and output frequency
F
out
[Hz]
08.05.2012
v_fxdm_setsig_min_max.vsd
1
2
3
4
5
6
7
8
9
10
Analog In 1
40
35
30
25
20
15
10
5
2
4
6
8
10
12
14
16
18
20
0...10 V
0...20 mA
10
20
30
40
50
60
70
80
90
100 0...100 % PWM
0
0
0
45
50
n-min OFF n-max. = 50 Hz
n-min 20 Hz n-max. = 45 Hz
n-min 10 Hz n-max. = 50 Hz
F
off
= 5 Hz
F
on
= 6 Hz
Fout:
Output frequency
Analog In:
Speed setting signal
n-min:
Min. Speed
n-max:
Max. Speed
Fo
ff
:
Shutdown Freq.
Fon:
Switch on Freq.
9.1.3
Touch function via external signal in mode
1.01
The output frequency can be set gradually via an external signal at the analog inputs
“
E1
”
and
“
E2
”
.
The following settings are required for this function:
•
Base setup
–
Mode:
1.01
–
E1 Analog In: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (je nach externem Signal)
–
E2 Function:
|
7E
|
–
E2 Analog In: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (je nach externem Signal)
•
IO Setup
–
E1 Mode:
|
3
|
–
E1 Min.: 0 - 100 % (setting as required)
–
E1 Max.: 100 - 0 % (setting as required)
–
E2 Mode:
|
3
|
–
E2 Min.: 0 - 100 % (setting as required)
–
E2 Max.: 100 - 0 % (setting as required)
–
Touch function.step: 0.00 - 100.00 % (setting as required)
Example: gradual setting via 0 - 10 V signal
Operating Instructions
Icontrol
–
model series FXDM
Programming
L-BAL-E036-GB 2022/47 Index 011
Part.-No.
33/108