Offset 1 for alarm during exceeding
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
ON
ON
ON = 15°C + 5 K = 20 °C
OFF = 20°C - 2 K = 18 °C
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
k
u
e
h
le
n
_
1
0
k
_
p
o
s
_
o
ff
s
e
t.
v
s
d
Example: Setpoint 15.0
°
C, 5.0 K, Hysteresis 2.0 K
Offset 2 for alarm during undercutting
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
OFF = 15°C + 2 K = 17 °C
ON = 20°C - 5K = 15 °C
ON
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
h
e
iz
e
n
_
9
k
_
n
e
g
_
o
ff
s
e
t.
v
s
d
Example: Setpoint 15.0
°
C, Offset -5.0 K, Hysteresis 2.0 K
9.12
Motor Setup
9.12.1
Setting motor rated current
MotorRatedCurr.
MotorRatedCurr.
Possible setting for the motor rated current.
The setting for the
“
DC brake level
”
(
setting brake behaviour) refers to this setting.
Setting range: 0.0...device rated current / A
Factory setting: device rated current
9.12.2
Setting motor rated voltage
MotorRatedVolt.
MotorRatedVolt.
When commissioning, you must set the motor to the rated voltage stated on the rating
plate.
Caution! Make settings for U/f curve and motor rated voltage only while the motor is not
being triggered.
Verify the output voltage using suitable measuring instruments.
Adjustment range: 0...270 V (settings above 270 V do not yield a higher output voltage)
Factory setting: 230 V
9.12.3
Adjustment of the U/f curve
Information
The device comes supplied with a preprogrammed square characteristic curve for the operation of
fans.
In the case of voltage-controllable motors and square load torque-moments (e.g. fans and pump
operation), an optimal speed control is generally achieved through this.
In systems in which high dynamics are required, switchover to a linear characteristic must take place.
Generally speaking, if the load characteristic is not known as a de
fi
nite value, the linear characteristic
should be set. In the case of linear characteristic curves, the motor achieves full torque throughout the
entire speed range. For this, a thermal overload of the motor must be prevented through suitable
measures (complete motor protection through using thermocontact or PTC thermistor-monitoring).
Edgefrequency
Edgefrequency
The maximum output voltage is attained during break edge frequency.
Adjustment range: 10.0 - 150.0 Hz
Factory setting: 50.0 Hz
Max. Frequency
Max. Frequency
Above the Edgefrequency, the frequency is merely increased up to the Maximum
frequency.
Adjustment range: 10.0 - 150.0 Hz
Factory setting: 50.0 Hz
Operating Instructions
Fcontrol
–
model series FXET4/6/10AMQ
Programming
L-BAL-E079-GB 1706 Index 008
Part.-No.
64/87