8
Start-up
8.1
Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the hazardous area.
8.2
Procedure for commissioning
Sequence
Setting
1
Switch position
“
0
”
(power stack switched off).
This prevents the system from inadvertently starting up before con
fi
guration is complete.
Settings for U/f characteristic can only be made when no motor modulation is present! This is the same also for
the setting of Mode.
2
If necessary, set the menu language in
Menu group
“
Start
”
.
(Factory setting Englisch:
“
Language GB
”
)
3
Set the operating mode in the
Base setup
menu group (factory settings
1.01
=
speed controllers
).
Attention!
When saving the operating mode, the respective preset factory operating-mode setting is loaded. That means,
the settings you have made, e.g., in
“
Motor setup
”
are lost. An exception: the menu language setting remains
preserved.
4
The
Motorsetup
factory installed values are for variable voltage external rotor motors 230 V / 50 Hz. After
checking of the motor data the setting are to be adapted if necessary. (rating plate)
5
Switch position
“
Auto
”
(power stack in operation).
Additional setings (
Programming and selected Mode).
Information
Digital input
“
Digital In 1
”
(terminals D1 - D1) factory setting for enable of device (ON / OFF) pre-
programmed (function
|
1D
|
IO Setup).
Operating Instructions
Fcontrol
–
model series FXET4/6/10AMQ
Start-up
L-BAL-E079-GB 1706 Index 008
Part.-No.