PINs
PIN
Function
PIN 0010
Opening service menu, if PIN-protection activated
PIN 1234
Opening
“
setting
”
.
if
“
set protection
”
=
“
ON
”
(
Controller Setup)
PIN 9090
Restore user setting
PIN 9091
Save user setting (corresponds function
“
Save user setup
”
=
“
ON
”
Controller Setup)
PIN 9095
Restore factory setting = delivery status
11
Diagnostics menu
Diagnostic
The diagnostics menu supplies information about the momentary operating condition
of the device.
00056:46:13
O
= Operation,
T
= Time,
C
= Controller
The time counting runs, as soon as mains voltage is connected (without fault).
If events step on (Motor fault, External Error, etc.), the period of operation is stored at
this time (
Events).
00056:46:13
O
= Operation,
T
= Time,
M
= Motor
The time counting runs as soon as a modulation of the controller is present
DC-Voltage
ZK voltage constant at approx. 400 V
The PFC (Power Factor Controller) makes it mostly independent of the mains voltage.
Heatsink
Display of the internal temperature of the power semiconductor. During impermissibly
high levels (at 75
°
C), the output power is automatically reduced. At 90
°
C switch off.
Capacitor
Display of DCLink Elco temperature. During impermissibly high levels (from 75
°
C on),
the output power is automatically reduced.
At 90
°
C switch off.
Filterchoke
Display of sine
fi
lter choke temperature. In case of temperature increase above prede-
termined threshold value the modulation is switched off. Restart when cooled down!
E1-KTY
Signal height at analog input E1 (Analog In 1)
E1-Current
E1-Voltage
E2-KTY
Signal height at analog input E2 (Analog In 2)
Operating Instructions
Fcontrol
–
model series FXET4/6/10AMQ
Diagnostics menu
L-BAL-E079-GB 1706 Index 008
Part.-No.
77/87