11 Enclosure
11.1 Technical data
Type
Part.-No.
Rated current
{1}
Max. line fuse
{2}
semiconductor fuse
{3}
Max. heat dissi-
pation approx.
{1}
Weight
[A]
[A]
[Part.-No.]
[W]
[kg]
PKE-6
303614
6
10
FF20 A 6x32 mm
(pack of 10 fuses:
349026)
15 W
0.6
PKE-10
303615
10
16
FF20 A 6x32 mm
(pack of 10 fuses:
349026)
25 W
0,8
PKE-14
303625
14
20
FF25 A
35 W
2.0
{1} with supply voltage of 230 V / 50 Hz, values for other speci
cations available on request
{2} Max. supply side line fuse according to DIN EN 60204-1 classi
cation VDE0113chapter 1
{3} Semiconductor fuse not in the scope of supply, as accessories available. For protection of damages in the case of short-
circuits installation on site recommended.
Line voltage
1 ~ 230 V (-15...+10 %), 50/60 Hz
Input resistance for sensor or signal set for the
rotational speed
for 0 - 10 V input: R
i
> 100 k
Ω
for 4 - 20 mA input: R
i
= 100
Ω
output voltage
approx. 0 - 100 % of applied mains voltage
Min. motor current
approx. 0.2 A
Voltage supply e.g. for sensors
+24 V
±
20 %, I
max
20 mA
Output (10 V)
I
max
10 mA (short-circuit-proof)
Max. permissible ambient temperature
40
°
C
Min. permissible ambient temperature
0
°
C (if mains voltage is not switched off up to -20
°
C)
Max. permissible installation height
0...4000 m amsl
Above 1000 m amsl the rated current is to be reduced by 5 % / 1000 m.
Permissible rel. humidity
85 % no condensation
Electromagnetic compatibility for the standard
voltage 230 / 400 V according to DIN IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)
Interference immunity EN 61000-6-2 (industrial applications)
Harmonics current according
In accordance with EN 61000-3-2
Up to a maximum current of 4 A, the limits are adhered to with no restric-
tions.
Housing protection
IP54
11.1.1
Performance reduction during elevated ambient temperatures
The maximum permissible ambient temperature for the devices is 40
°
C. Up to this temperature, loading (maximum continuous
current) with the speci
ed rated current is possible.
The removal of heat in the unit due to power dissipation is dependent on the ambient temperature, so the maximum load has to
be reduced if the ambient temperature is higher than 40
°
C! For each degree higher the load has to be reduced approx. 2.2 %.
The average value measured during a 24 h period must be 5 K under the max. ambient temperature. For installation in a switch
cabinet, the device
’
s dissipation and its possible affect on the ambient temperature must be taken into consideration (
F
Technical data)!
Maximum load for ambient temperatures higher 40
°
C
Type
Part.-No.
Rated current for 40
°
C
max. current load for 50
°
C
max. current load for 55
°
C
[A]
[A]
[A]
PKE-6
303614
6
4.5
4.0
PKE-10
303615
10
7.0
6.0
PKE-14
303625
14
12.0
10.0
Operating Instructions
Acontrol
–
model series PKE-6 /-10 / PKE-14
Enclosure
L-BAL-E042-GB 1002 Index002
Part.-No. 00163314-GB
21/26