6 Operating and display elements
28.08.2008
v_pke_bedien_anzeige.VSD
V
°C
mA
E1
%
0
100
n-min
%
0
100
R47
set
ON
OFF
4
3
2
1
S1
V13
R
4
8
n-max /
P-band
R
4
9
%
5
30
Potentiometer
set
Function dependently on selected mode of operation
•
For
Speed controller
1.01
without function.
•
For
temperature control
2.01
with passive sensors TF.. (KTY).
setting range: 0 - 100 %
≙
-26...76
°
C (measuring range of controller).
•
For
control with active sensors
3.01
, (0 - 10 V, 4 - 20 mA).
Setting range: 0 - 100 %
≙
measuring range of sensor.
Potentiometer
n-min
Minimal output voltage (basic speed)
Setting range: 0 - 100 % (
“
n-min
”
takes priority if over
“
n-max
”
)
Potentiometer
n-max / Pband
Function dependently on selected mode of operation
•
For
speed controller
1.01
Maximal output voltage speed limiter:
–
Setting range: 100 % -
“
n-min
”
(100 % output voltage = fully clockwise position 30 %)
•
For
P-Controller
,
2.01
,
3.01
Pband (control range)
–
For
temperature control with passive sensors TF.. (KTY).
Setting range: 5 - 30 %
≙
5.1 - 30.6 K.
–
For
control with active sensors (0 - 10 V, 4 - 20 mA).
Setting range: 5 - 30 %
≙
5 - 30 % measuring range of sensor.
Dipswitch
S1
Basic setting for device function
Status LED
V13
Indicate the operating conditions over
ashing code
Jumper
E1
Basic setting for kind of signal at analog input
“
E1 = Analog In 1
”
Operating Instructions
Acontrol
–
model series PKE-6 /-10 / PKE-14
Operating and display elements
L-BAL-E042-GB 1002 Index002