Repairs of electrical parts and refrigeration circuit only carried out

Trouble Shooting

by a qualified technician!

Malfunction

Cause

Remedial Action

Melt-water in storage bin

Melt-water drain blocked

Clean, rinse with water

does not flow off

Machine is sited below

Raise machine or lower drain

drain level

Install melt water pump
(ask Ziegra)

Water-Leakage

Hose connections loose or defective

Fasten, insert new seals or replace

Water runs into machine or 

Lid of water chamber loose

Reset correctly

onto floor

Melt-water drain loose

Fasten clamp

Fissure in water chamber

Replace

Water leaks from the ice 

Shaft seal in cylinder defectiv

Replace

maker

Water pressure switch or

No water in water chamber

Check water supply

Waterlevel control

Water pressure:  min 1 bar  -  max 5 bar

has switched off

Clean water filter and float valve

High pressure switch

* Air in refrigeration circuit

Change filter drier

has switched off

(insufficiently evacuated 

evacuate circuit

after repair)

refill refrigerant

*  ambient temperature too high

Machine must not be placed in
the sun or too warm ambience.
Improve ventilation.

*  condensor soiled

Clean with brush or compressed air.

*  ventilator motor

defective

Check / replace

Machine does not work
General electrical faults

*

Absence of current

Check socket and fuses

*

Intermittent contact

Check electrical connections,
also in control panel

*

Water pressure switch defective 

replace

*

Water level switch does not work

Check, adjust metal tongue if necessary

*

Ice switch does not work

Check, see below

Overload cut-out 

Motor overload caused by

has switched off

*

electric capacitor of gear

replace

   

motor defective

*

gear defective 

replace 

* cylinder bearing damaged

replace 

* machine freezes up

see "machine freezes up" 

* ice breaker misadjusted 

see "cleaning of freezing unit"

   

(ZBE 30 - ZBE 110)

* overload cut-out defective

replace

Storage bin thermostat does not

* Ambient temperature too low

Choose different locations or increase

switch or switches too early

ambient temperature.    Instant remedy:
warm thermostat by hand.

* Thermostat defective or 

replace or Re-Set

setting incorrect

off: approx. 1 min. after ice contact
on: at +5° C

Ice switch 

does not work

jammed (or defect)

adjust (or replace)

5

                    

Summary of Contents for ZBE 110

Page 1: ...quality Miscellaneous 6 Freezing unit 7 Refrigerant and water cicuits 8 wiring diagram attached General installation advice Assembly Instruction Freezing unit Spare parts list Subject to technical modifications Edition 07 8 09 ZIEGRA EISMASCHINEN Germany 30901 Isernhagen www ziegra com Service Tel 49 0511 90244 0 Tel 49 0511 90244 18 Fax 90244 90 Fax 90244 92 ice ziegra com service ziegra com ZBE ...

Page 2: ...ing auger does not form part of the refrigeration circuit Therefore leakages in the refrigeration system caused by rotating parts cannot occur The ideal ice temperature is 0 5 C Ziegra chip ice has the ideal temperature of 0 5 C It is irregular and crystalline in structure and always stays loose In contrast with other types of ice it can be stored without being sub cooled and never freezes up Zieg...

Page 3: ...ke firm installation to main is outside 7 2 9 5 pH consult Ziegra power supply Provide main switch 3 phase machines have a supplied with m c 2 m high pressure hose an phase sequence relay 3 4 sleeve for water inlet Other voltage according to order type plate wiring Provide at side Water pressure 1 5 bar diagram stop valve and strainer If long supply lines necessary insulate if possible 5 Storage b...

Page 4: ...in case of too low water pressure or water shortage Automatic restart when the water supply has been restored 4 Compressor Automatic motor cut out in compressor connecting box 5 High pressure switch The machine is switched off if there is e g excess in the refrigeration system caused by too high ambient temperature or soiled condenser 6 Gear Motor Overload cut out in switch box 7 Automatic water d...

Page 5: ... ZBE 110 lift grid and take it off All parts getting in contact with ice ZBE 150 ZBE 375 remove lid ice hose into storage and front panel ice discharge interior or exterior Ice storage melt water grid General check Any water leaks melt water drain The machine runs quite ice scoop Small parts After being thorougly cleaned Every 2 5 years can also be given into dishwasher check cylinder bearing Scal...

Page 6: ... ambient temperature too high Machine must not be placed in the sun or too warm ambience Improve ventilation condensor soiled Clean with brush or compressed air ventilator motor defective Check replace Machine does not work General electrical faults Absence of current Check socket and fuses Intermittent contact Check electrical connections also in control panel Water pressure switch defective repl...

Page 7: ...runs in intervals see above refrigeration unit stopped If Ice maker is connected no sufficient refrigerant check the cooling system of the to a central refrigeration unit Suction pressure too low central refrigeration unit Machine runs in intervals pressure fluctuation Data must comply to the ZIEGRA prescription If not at hand ask Ziegra Rumbling or loud squeaking Air bubble in pipe between water ...

Page 8: ...ber and the freezing unit into a container o Connect a hose of appr 80 cm with funnel at the water inlet of the freezing unit o Mix cleaning agent with hot water 1 3 bottle agent in 3 4 litre water of appr 50 C o Fill the freezing unit with cleaning agent up to the ice discharge level o Allow the cleaner to react for 10 15 minutes A maximum of 30 minutes must not be exceeded The cleaner first remo...

Page 9: ...Refrigerant and Water Circuit 8 ...

Page 10: ...l 01759 301142 Fax 01759 301143 sales wolflabs co uk Use the above details to contact us if this literature doesn t answer all your questions Pricing on any accessories shown can be found by keying the part number into the search box on our website ...

Reviews: