6
Description
RAYSTAT-ECO-10 is an electronic controller with display, advanced alarm
facilities and the capability of switching large currents.
The RAYSTAT-ECO-10 is designed to control heating cable systems. Heat-
ing cable can be controlled either directly by the RAYSTAT-ECO-10 or via a
contactor.
Direct switching of heating cables is possible for heating loads up to 25 A.
For heating loads greater than 25 A indirect switching via a suitably rated
contactor controlled by a RAYSTAT-ECO-10 is necessary.
Installation and all wiring must be in accordance with applicable regulations.
The device must be installed in non hazardous areas only.
Tyco Thermal Controls offers other controls for use in hazardous areas.
Technical data
Supply voltage:
230 Vac. +10%/–10%, 50/60 Hz (6V leakproof
maintenance-free non-rechargeable battery
incl. for programming without power supply)
Main relay:
max. 25 A, 250 Vac. Resistive
Heater operation on
sensor error:
programmable: ON or OFF
Set point T range:
0°C to + 30°C
Accuracy:
±0,5 K at 5°C
Operatingtemperature: –30°C (–20°C, VDE approved) to +40°C ambient
User interface:
4 x 7 segment digital display
4 push buttons
alarm relay, max. 2 A, 250 Vac. (Potential free)
Power terminals:
3 x 0,75 mm
2
to 4 mm
2
Alarm terminals:
(3 + ) x 0,75 mm
2
to 2,5 mm
2
Sensor terminals:
(3 + ) x 0,75 mm
2
to 2,5 mm
2
Heater terminals:
(2 + ) x 0,75 mm
2
to 4 mm
2
Enclosure
Exposure Temperature: –40°C to +80°C
Ingress Protection:
IP 65
Entries:
2 x M25, 1 x M20, 1 x M16
Size:
120 x 160 x 90 mm
Weight:
approx. 800 gr.
Material:
polycarbonate
Lid fixing:
4 captive screws
Mounting:
on a wall or directly on the pipe using support
brackets, SB-100 / SB-101
Summary of Contents for DigiTrace RAYSTAT-ECO-10
Page 3: ...3 V D E A 8 3 2 4 6 5 9a 1 9b ...
Page 4: ...4 B 1 2 3 4 5 6 ...