13
4. Errors
RAYSTAT-ECO-10 can differentiate between 5 errors. The error is displayed
as soon as the error condition is detected. The alarm relay switches at the
same moment. The value display indicates “ ” (flashing) and the status
display indicates the error number.
Error Code
Description
Remedy
Short Circuit Sensor
Replace sensor
(or very low resistance)
Open Circuit Sensor
Connect sensor cable or
replace sensor
Temperature below
Verify appropriateness
Min. Expected Ambient
of setting
Output Voltage Error
1
Relay or triac malfunction /
replace unit
Supply below 207 Vac.
2
Verify supply voltage
1
Detection of this error is disabled in Voltage Free Mode.
2
Unit is not active when supply voltage is below approx. 190 Vac.
All alarms are on the same alarm relay.
An alarm will clear automatically as soon as the error condition is gone.
There is no need to reset; all settings are maintained.
If multiple alarms are active, the alarms are shown with the following prior-
ity:
(Highest),
,
,
,
(Lowest)
Note:
is not applicable to RAYSTAT-ECO-10.