background image

95

Chapter 2, OPERATION

Step 5:  Remove the front panel.
Step 6:  Clean the inside of the heater.

Before starting to clean the heater, ensure
that the interior is cool enough to touch.
Wipe all dust off the outside of the housing
with a clean, non-fluffy, damp cloth or
another suitable cleaning aid. Do not forget
to clean the outside of the heat chamber
and the heat exchanger.

Step 7:  Re-attach the front panel.
Step 8:  Insert the heater plug into the socket.
Step 9:  Switch the heater ON.
Step10: Re-programme the heater 

(clock and set-back timer).

Attention: If the heater overheats after the completion
of a recovery procedure, contact your dealer and do
not switch the heater on until the problem has been
resolved.

13. Cleaning the filter (monthly)

The filter of the fuel pump must be cleaned each
month and at the end of the heating season.
a) Open the flap on the right of the heater.
b) Close the cut-off valve on the fuel pipe.
c) Place the fuel collecting gutter under the float

house in order to prevent fuel spills. Collect the fuel
in a container.

d) Unscrew the plate covering the filter.
e) Remove the filter and clean it carefully with

compressed air. 

f) Replace the filter and screw the covering plate back

into position.

g) Wipe away the spilled fuel.
h) Open the cut-off valve in the fuel pipe. Ensure that

there are no fuel leaks.

Note: At the end of the heating season, remove any
fuel remaining in the float house by unscrewing the
drain plug.  

14. Before consulting an expert

The following situations do not indicate defects.

While switching the heater on or off

White smoke can be seen when the heater is switched
on for the first time.
Machine oil or dust on the burner chamber or heat
exchanger is burning.

The flames flicker for several minutes after the heater
has been ignited.
The ignition rod continues to function when the heater
is cold, even several minutes after ignition. This may
cause the flames to be a little larger.

The heater makes intermittent creaking sounds when
warming up or cooling down.
Expansion and shrinkage of metal parts may cause a
slight creaking sound.

Circulation of air in the room does not start immediate-
ly when the heater is lit.
To prevent unpleasant cold draughts, the ventilator
only switches on when the heater has become warm.

A loud clicking sound can be heard during the first use
or when the fuel runs out.
There is air in the fuel pump. This should be gone with-
in approximately 1 minute.
If the clicking sound in the fuel pump does not stop
after approximately 1 minute, push the red ‘reset’ but-
ton on the float chamber (do not hold it in). Also check
whether all the fuel valves are open, the fuel filters are
clean and whether there is sufficient fuel.

Note: The fuel pump may make a slight ticking sound
during normal operation. This does not indicate a prob-
lem.

While the heater is in operation

A part of the burner pot and/or heat exchanger
becomes red in colour during operation.
This is normal and does not indicate a problem.

Summary of Contents for Laser 56

Page 1: ...Laser 56 3 27 51 75 98 122 MANUEL D UTILISATION GEBRAUCHSANWEISUNG BRUGSANVISNING OPERATING INSTRUCTIONS ISTRUZIONI D USO GEBRUIKSAANWIJZING 3 2 6 4 1...

Page 2: ...course provided you use the heater correctly Please read these Directions for Use first to ensure maximum lifetime for your Zibro Your heater comes with a 24 month manufacturer s warranty on all defe...

Page 3: ...not have optimum burning in such rooms Do not use the heater in the immediate surrounding of a bath a shower or a swimming pool 4 Switch off the heater before you leave or go sleeping Unplug the heate...

Page 4: ...se Check the gaps in the manner stipulated in the instructions in the manual Recommended tool kit 1 Crosshead screwdriver 2 Steel tape measure 3 Felt tip pen or pencil 4 Cement for exterior use 5 Elec...

Page 5: ...e future trans portation A Remove the cardboard drilling template and the user s manual from the packaging B Remove the base plate and the box with the installation kit from the packaging C Remove the...

Page 6: ...cm Not less than 45 cm Not less than 45 cm Frontal obstruction 45 cm or more 50 cm or more Snow covered surface or ground Important The gap with the ground must be enlarged in areas subject to heavy...

Page 7: ...e are the dimensions and locations of the holes for the fuel pipe and exhaust pipe Do not remove any components from the heater Always contact your dealer if repairs are required If the electricity ca...

Page 8: ...ist of standard installation parts is sup plied with your heater It may be necessary to order extra parts from your Zibro dealer if other installation methods are required Base plate 1 Wall hooks 2 se...

Page 9: ...Chapter 1 INSTALLATION 82 Right angled exhaust pipe bend 1 Discharge chute 1 Right angled air hose 2 Flexible air hose 1 Hose clip 2...

Page 10: ...e the heater can be levelled by means of adjustable legs This can be checked with the plumb line 2 Drill the hole for the exhaust pipe Use a hole saw with a diameter of 70 80 mm see Fig 5 The opening...

Page 11: ...Install the inner flue pipe a For wall thickness 230 320mm From inside the room insert the inner flue pipe through the hole Make sure the arrow on the inner flue pipe is pointing up Secure the inner f...

Page 12: ...the right angled air hose onto the inlet with a hose clip Seal the inlets and outlets that are not being used with the caps supplied Check that the caps are firmly in position See Fig 10 Use water or...

Page 13: ...he right angled air hose to the inlet Check that everything is firmly attached See Fig 12 Fig 12 Outlet Inlet Right angled exhaust bend Right angled air hose 5 In case the circuit board cover gets in...

Page 14: ...ing the pipe lock into the outlet clip See Fig 13 Fig 13 Pipe holder Pipe lock 8 Installation of an external fuel tank The installation of an external fuel tank is illustrated in a diagram Fig 1 11 Th...

Page 15: ...ever use benzene LPG camping gas or other flammable liquids The use of these substances may cause explosions or fire Available fuel supply options The fuel supply of the Laser 56 can be set up as foll...

Page 16: ...s free of dust and waste particles These particles may cause problems in the fuel receptacle Copper tubing with an exterior diameter of 3 8 must be used for the fuel pipe The installation of the exter...

Page 17: ...system All specified operating procedures must be carried out in the order in which they are described 2 Laser 56 heater specifications Nominal yield as applied to petroleum heaters 93 Power consumpti...

Page 18: ...and you wish to see a time indication return the selector switch to the normal position The start and finish times of SET BACK timer are also set with this switch 6 Information display Displays the c...

Page 19: ...manual operation If the heater is in AUTO mode switch the AUTO switch to OFF to change to MANUAL operation Step 2 Switch the heater ON Press the ON OFF button until ON is displayed The current room t...

Page 20: ...hown in the information display e g PM 10 00 Step 2 Set the finish time of the SET BACK mode While the time selector switch is in the END SET BACK mode you must now programme the finish time in the sa...

Page 21: ...e plug out of the socket after the on off light has switched off if the heater will not be used for an extended period of time 11 Power cuts recovery system If a power cut occurs while the heater is i...

Page 22: ...ning in the float house by unscrewing the drain plug 14 Before consulting an expert The following situations do not indicate defects While switching the heater on or off White smoke can be seen when t...

Page 23: ...fuel sup ply to a maximum of 2 5 PSI 0 17 bar Float mechanism does not work Contact your dealer Poor noisy combustion Soot formation in the exhaust pipe Remove the soot from the exhaust pipe Burner r...

Page 24: ...f purchase provided no changes have been made to it The warranty shall not apply to damages caused by actions not in compliance with the Directions for Use neglect and the use of an incorrect type of...

Page 25: ...ro com 3 FRANCE PVG France SARL 4 Rue Jean Sib lius B P 185 76410 SOTTEVILLE SOUS LE VAL tel 33 2 32 96 07 47 fax 33 0 820 34 64 84 email pvgfrance zibro com 4 UNITED KINGDOM Lister Gases Bridge Stree...

Reviews: