Powering Up the Network Extender 

The DC power terminal block on the network extender has five terminals: two positive, 
two negative, and one with no connection (NC).  Only one positive terminal and one 
negative terminal pair need to be connected for operational purposes. The second 
positive and negative terminal pair may be connected to a backup DC power supply for 
redundancy purposes. There is also a system ground terminal on the back panel above 
the power connector.  Connect this terminal to a reliable source of ground.  The ground 
terminal must always be connected regardless of the powering connections. DO NOT 
OPERATE THE NETWORK EXTENDER WITHOUT A GROUND CONNECTION. 

 

 

Procedure 

Power Connection - Grounding 

1.  Connect a copper wire of at least 18 AWG from a ground source to the ground 

lug on the back of the unit.  In Telco central office installations, the ground source 
must be a Common Bonding Network (CB-N). 

2.  The ampacity of the ground conductor shall be equal to, or greater than, the 

ampacity of the conductor connected to the DC power connection’s DC return. 

3.  Strip the end of the ground wire.  The bare stripped ends of the ground conductor 

must be coated with an anti oxidation compound before crimp connections are 
made to connector terminals. Crimp a connector (of a size suitable to fit the 
ground lug on the chassis) onto the prepared wire end.  Use only listed 
connection terminals on the ground wire. 

4.  The ground lug on the unit has two nuts with a star washer between them. 

Remove the outer nut and star washer, put the ground connector (prepared in 
step 3 above) over the ground stud on the chassis.  Replace the star washer on 
the stud, then the nut.  Tighten the nut so that the ground connection is secure 
and will not rotate. 

 

Power Connection – DC Power 

1.  Loosen all screws at the top of the power terminal strip. 

2.  Insert your –48 VDC lead into the negative (–) terminal of one of the terminal 

pairs. Tighten the screw for that terminal. 

3.  Insert your 48 VDC return lead into the positive (+) terminal of the same terminal 

pair as in Step 2. Tighten the screw for that terminal.  

4.  Repeat Step 2 and Step 3 for the free pair of power terminals if you have a 

redundant power supply. 

5.  Plug the power terminal strip into the power connector on the back of the unit. 

6.  Verify that the Power LED on the front of the network extender is illuminated. 

 

   

Summary of Contents for ETHX-2214-DS3

Page 1: ...4 DS3 and ETHX 2224 DS3 4 Package Contents 6 Release Notes 6 Product Documentation Online 6 Powering Up the Network Extender 7 Connecting the DS3 Lines 9 Connecting the Ethernet Lines 11 LED Indicators 12 Web Interface 14 Command Line Interface 19 Resetting the Network Extender to Factory Defaults 21 Specifications 23 Safety Notices 24 EMI Notices 24 NEBS Compliance 24 Service and Repair 25 Import...

Page 2: ... including any copy of either If you have executed a separate written agreement covering the Software supplied to you under this purchase such separate written agreement shall govern Zhone Technologies Inc Zhone grants to you and you Licensee agree to accept a personal non transferable non exclusive right without the right to sublicense to use the Software solely as it is intended and solely as in...

Page 3: ...tion to another 6 IN NO EVENT WILL ZHONE BE LIABLE TO LICENSEE FOR ANY CONSEQUENTIAL INCIDENTAL PUNITIVE OR SPECIAL DAMAGES INCLUDING ANY LOST PROFITS OR LOST SAVINGS LOSS OF BUSINESS INFORMATION OR BUSINESS INTERRUPTION OR OTHER PECUNIARY LOSS ARISING OUT OF THE USE OR INABILITY TO USE THE SOFTWARE WHETHER BASED ON CONTRACT TORT WARRANTY OR OTHER LEGAL OR EQUITABLE GROUNDS EVEN IF ZHONE HAS BEEN ...

Page 4: ...throughput capacity than a traditional DS3 circuit Zhone s loop bonded technology provides automatic load balancing and fail over for optimum redundancy and data throughput To maximize the total bandwidth available for ethernet traffic the ETHX 22x4 DS3 devices operate in a DS3 framer bypass mode i e the ethernet traffic is mapped onto the entire 44 736 Mbps of each DS3 facility including any over...

Page 5: ...e Provider Mode ETHX ETHX 2214 2214 Subscriber Mode Subscriber Mode ETHX ETHX 2214 2214 Subscriber Mode Subscriber Mode Ethernet over DS3 Ethernet over DS3 45 Mbps 45 Mbps Ethernet over DS3 Ethernet over DS3 45 Mbps 45 Mbps ETHX ETHX 2214 2214 Provider Mode Provider Mode ETHX ETHX 2214 2214 Subscriber Mode Subscriber Mode Ethernet over DS3 Ethernet over DS3 45 Mbps 45 Mbps ETHX ETHX 2224 2224 Prov...

Page 6: ...stead please contact your local sales representative service representative or distributor Please refer to the Service and Repair section of this manual for additional support and contact information Release Notes Before installing your network extender you should update to the latest firmware load and review the associated release notes for your model These are available for download on the Servi...

Page 7: ...rip the end of the ground wire The bare stripped ends of the ground conductor must be coated with an anti oxidation compound before crimp connections are made to connector terminals Crimp a connector of a size suitable to fit the ground lug on the chassis onto the prepared wire end Use only listed connection terminals on the ground wire 4 The ground lug on the unit has two nuts with a star washer ...

Page 8: ...roved for use in powering the unit Using any other AC power supply could cause the unit to be non compliant to emissions and safety regulations 2 Plug the power terminal strip into the power connector on the back of the unit 3 Plug the AC power cord into the AC power supply and into a compatible AC outlet 4 Verify that the Power LED on the front of the network extender is illuminated ...

Page 9: ...he ETHX 2224 DS3 device can be operated with just one of the two DS3s connected or can be used in loop bonded applications where both DS3 circuits are utilized Each DS3 port requires the use of two 2 75 ohm BNC connectors one each for transmit and receive signals Tx Rx 10 100 ETHERNET 48VDC 0 45A 1 2 3 4 NC DS3 Tx Tx Rx Rx 10 100 ETHERNET 48VDC 0 45A 1 2 3 4 NC DS3 ...

Page 10: ...shed and operational Refer to Table 2 on page 12 for a description of the DS3 LED indicators Dual DS3 Loop Bonded Connections Using two DS3 lines for one network connection loop bonding effectively doubles the speed and data throughput capability of the network extender Two DS3 lines also act as a backup should one of the lines become disabled Procedure 1 Plug the DS3 cables into the DS3 BNC 75 oh...

Page 11: ...le into one of the 10 100 ETHERNET ports on the back of the network extender A straight through cable can be used for all applications 2 Verify the Ethernet connection After connecting the other end of the Ethernet cable to a suitable device a solid green illumination of the corresponding 10 100 ETHERNET Connection LINK ACT Link Activity LED on the front of the network extender indicates a connect...

Page 12: ...rect connection has been lost the unit may no longer be receiving data from its partner network extender Blue alarm The unit s partner network extender has lost a connection with an intermediate device and has LOS or RAI Flashing Amber Data is being transmitted DS3 Connections Tx Ports 1 or 1 2 Not Illuminated No data is being transmitted Flashing Amber Data is being received DS3 Connections Rx Po...

Page 13: ...minated No Ethernet connection The Ethernet 100 and Act LEDs will remain unlit by default Solid Amber Full duplex Ethernet connection Not Illuminated No link or functioning at half duplex 10 100 Ethernet Connections Duplex Collision Pulsing Amber Half duplex link with packet collisions Solid Green 100 Mbps Ethernet connection is established If the Ethernet 100 LED is illuminated the Ethernet Lnk A...

Page 14: ...dth or height of the screen To verify screen resolution on a Windows system Right click on your Desktop Select Properties Click the Settings tab Adjust the Screen Resolution as needed Configuring a Windows PC to Communicate with Web Management To communicate with web management the Ethernet interface on your PC must be on the same subnet as the network extender For example to configure the IP addr...

Page 15: ...mber between 3 and 250 inclusive in the IP Address field 7 Type 255 255 255 0 in the Subnet Mask field 8 Click on OK twice to confirm your changes and close the Control Panel 9 Start your web browser Type 192 168 254 252 for a Provider unit or 192 168 254 251 for a Subscriber unit into the Address field and press Enter The web server opening screen appears 10 Click on Next The login dialog box app...

Page 16: ...ia the Internet Refresh Screen Refreshes web management screen Ethernet Connections Lnk Act LEDs Ethernet Duplex Mode Speed and Native VLAN ID DS3 Connections Lnk Alm LEDs DS3 Circuit Configuration DS3 Tx Buildout and Clock Source etc Filter Configuration DSCP Rules IP Rules MAC Rules VLAN Rules Flood type Port Statistics and Port Copy Using Web Management to managing a Provider Unit To manage a P...

Page 17: ...un In the open window type CMD and press Enter At the command line type arp s 192 168 254 251 xx xx xx xx xx xx where the IP address is the default address of the Subscriber unit and the MAC address is the number on the bottom label For example if the MAC address on the bottom label is 00 50 ca 01 28 86 type arp s 192 168 254 251 00 50 ca 01 28 86 Once the ARP table entry is configured you can pin...

Page 18: ...he Zhone Logo It will display either the word Provider or Subscriber indicating the current mode of the unit To make a change click on the Pro Sub Cfg button which is located just left of center on the graphical view of the front of the unit This will bring up the following screen Click on one of the radio buttons associated with the desired mode for the unit Then click on the submit button Go bac...

Page 19: ...the CLI Microsoft Windows Operating Systems 98 2000 NT and XP include a Telnet client which is run using the Windows command prompt cmd exe If you are using an operating system other than Windows you may need to install a Telnet client Connecting a PC Directly Initial configuration using the CLI requires a direct physical connection from your PC to the COM port of the network extender you are conf...

Page 20: ...e CLI to Establish In band Management Option 1 After you have logged in enter a question mark to list the available commands CLI Set commands are used to establish in band management For example set slot 1 ip_address 137 182 10 251 set slot 1 subnet_mask 255 255 255 0 set slot 1 default_gateway 137 182 10 10 The Subscriber unit in this example can now be managed with web management by attaching a ...

Page 21: ...ed paper clip to gently push the button and let it go 2 Wait a few seconds until the DS3 Port LEDs flash green starting at Port 1 and ending at Port 2 on an ETHX 2224 DS3 unit Gently push the reset button again within 3 seconds of port 1 or port 2 LED illumination NVRAM is cleared and all configurations on the unit are set to the factory defaults Note As mentioned previously the factory default fo...

Page 22: ...Pin Assignments To connect the COM port to the DB9 serial port of a PC use an adapter wired as shown Table 5 DB9 to 8 Pin Modular Adapter Pinouts Pin 8 Pin Modular Port Direction PC RS232 Serial Port Pin 1 Transmit Data TxD RxD Receive Data 2 2 Data Set Ready DSR RTS Request to Send 7 4 Receive Data RxD TxD Transmit Data 3 5 Ground GND GND Ground 5 6 Data Terminal Ready DTR CTS Clear to Send 8 Not...

Page 23: ... Environment Temperature 40 F to 158 F 40 C to 70 C Non operating temperature 40 F to 158 F 40 C to 70 C Humidity 5 to 95 non condensing Altitude 200 ft to 16 500 ft 60 m to 5 000 m Power ETHX 2214 DS3 48 VDC 0 2 A 10 W ETHX 2224 DS3 48 VDC 0 3 A 15 W Protocols Supported Transparent 802 1D Bridging DS3 Line Code unframed and unchannelized DS3 only M13 and C Bit DS3 Framing formats are not supporte...

Page 24: ...ser will be required to correct the interference at their expense The authority to operate this equipment is conditioned by the requirements that no modifications will be made to the equipment unless the changes or modifications are expressly approved by Zhone Technologies Inc If the equipment includes a ferrite choke or chokes they must be installed per the installation instructions Canada EMI No...

Page 25: ...ce representative or distributor directly for any help needed For additional information concerning warranty sales service repair installation documentation training distributor locations or Zhone worldwide office locations use one of the following methods Internet Visit the Zhone World Wide Web site at www Zhone com Telephone Call our automated system to receive current information by fax or to s...

Page 26: ...gs are interconnected the voltage potential may cause a hazardous condition Consult a qualified electrical consultant to determine whether or not this phenomenon exists and if necessary implement corrective action prior to interconnecting the products 7 Input power to this product must be provided by one of the following 1 a UL Listed CSA certified power source with a Class 2 or Limited Power Sour...

Page 27: ...27 Copyright 2008 Zhone Technologies Inc Printed in U S A ...

Page 28: ...28 ETH3 A2 ZN10 10 830 01728 02 ...

Reviews: