ZGR VERSATILE RT - 10 KVA
Manual de operaciones
www.zigor.com
22
4
INSTALLATION
Unpack checking
packaging.
Check the appearance to see if the UPS is damaged during transportation, do not switch on the UPS if any
damaged is found and please contact the dealer.
Check the accessories according to the packing list and contact the dealer if any parts missing.
Mechanical installation
•
Please place the UPS in a clean, stable environment, avoid the vibration, dust, humidity, flammable gas
and liquid, corrosive objects. To avoid from high room temperature, a system of room extractor fans is
recommended to be installed. Optional air filters are available if the UPS operates in a dusty environment.
•
The environment temperature around the UPS should keep in a range of 0
℃
~
40
℃
. If the environment
temperature exceeds 40
℃
, the rated load capacity should be reduced by 12% per 5
℃
. The max
temperature can't be higher than 50
℃
.
•
If the UPS is dismantled under low temperature, it might be in a condensing condition.The UPS can't be
installed unless the internal and external of the equipment is fully dry. Otherwise, there will be in danger of
electric shock.
•
Batteries should be mounted in an environment where the temperature is within the required specs.
Temperature is a major factor in determining battery life and capacity. In a normal installation, the battery
temperature is maintained between 15 °C and 25 °C. Keep batteries away from heat sources or main air
ventilation area, etc.
•
Should the equipment not be installed immediately it must be stored in a room so as to protect it against
excessive humidity and or heat sources.
•
The highest altitude that UPS may work normally with full load is 1500 meters. The load capacity should
be reduced when this UPS is installed in place whose altitude is higher than 1500 meters, shown as the
Table 4-1:
From then on, the customer will have 24 hours to make any claim under guarantee for any anomaly in the
amount or quality of the products received, providing details of the material received in bad condition after
reporting this circumstance on the forwarding agent's delivery note on reception.
Should the customer not report any defect within 24 hours, it will be understood that he has accepted delivery
of the unit.
WARNING
Ensure that the weight of the unit is within the maximum load limits (kg) of the tools used in order to handle it
and the supports used to secure it in place. Review weight details in the specifications of the ZGR
VERSATILE RT - 10 KVA.
WARNING
Typical battery performance data are quoted for an operating temperature between 20°C and 25°C. Operating it
above this range will reduce the battery life while operation below this range will reduce the battery capacity.
WARNING
An unused battery must be recharged every 3months. Temporarily connecting the UPS to a suitable AC supply
and activating it for the time required for recharging the batteries are required.