ZGR VERSATILE RT - 10 KVA
Manual de operaciones
www.zigor.com
17
Fig. 3-14
Setting menu
Press OFF key to enter test now Test Now, press
to select test value and press OFF to confirm. The
Battery manual test command can test battery discharge for 10 s, 10 min and to End of Discharge EOD.
(Fig. 3-15).
Fig. 3-15
Setting/Test Now menu
9)
MAINTENANCE: Press
+ OFF key to enter maintenance and display a password window. This setting
is only accessible by authorized personal. Contact ZIGOR for training. (Fig. 3-16).
Fig. 3-16
Setting/Maintenance menu
10)
MAINTENANCE SYSTEM: Press OFF key to enter item and confirm value, press
change value (Fig.
Work mode: Normal, Paralado, ECO
V_Output Grade: 220/230/240 V
F_Output Grade: 50 and 60 Hz
F_mode: CVCF and Non-CVCF (Fecuency converter)
Test type: 10 s, 10 min and EOD
Test Cycle: 1~30 days
Equipment ID: Device address is 1~15, it is the MODBUS device address used for RS232 & RS485
communication ports.
①
Press
to set the address 1~15. When battery temperature sensor is open,
c
parallel ID.
②
parallel ID setting. (Note: Under single UPS mode, until this device address setting save and exit, single