ZGR VERSATILE RT - 10 KVA
Manual de operaciones
www.zigor.com
18
UPS setting is done.)
Temp. Sensor SW: ON or OFF. OFF means turn off the sensor switch, ON means turn on the sensor
switch, send query command to sensor with address 11,12 every second.
Fig. 3-17
Setting/Maintenance - System menu
11)
MAINTENANCE BYPASS: Press OFF key to enter item and confirm value, press
change value (Fig.
This menu defines how the static bypass will work. This limits will will lock/unlock bypass transfer.
Fig. 3-18
Setting/Maintenance - Bypass menu
12)
MAINTENANCE BATTERY: Press OFF key to enter item and confirm value, press
change value
Number: 16/18/20 PCS Total (Note: there are 8/9/10pcs between Bat+ / BatN string
BatN / Bat-
string)
Capacity: 7~2000Ah
Boost charge: Enable or disable
Group: 1~8
V-Boost: 2,30~2,40, step is 0.01V
V-Float: 2,20~2,29, step is 0.01VV-EOD:1,75V o 1,80V
I-Maxcharge: 1~10A
Fig. 3-19
Setting/Maintenance
– Battery menu
13)
MAINTENANCE PARALLEL: This item can be selected after the work mode is set to parallel. Press