Web Server
~
16
~
Fig. 5-5: Set Active Power Limitation Method
The following ways will introduce how to configure the three kinds of power
limitation.
For correct operation of this method the parameter: tem A – total inverter AC
capacity of PV system that must be entered, please refer to Fig. 5-6:
Based on the Installed Inverter AC Capacity
In this method the AC output of the PV system will not exceed a set percentage
of the installed inverter AC capacity. For example, if a 20 % limitation on a 3
kWp PV system connected to an
Zeverlution 3000S
has been set then the AC
output will not exceed 0.6kWac.
Click the “OK” button in bottom-right of this web page to ensure the setting
parameters take effect.
The Fig. 5-6: Set parameters based on the AC capacity