Zeva BMS16v3 Manual Download Page 2

ZERO EMISSION VEHICLES AUSTRALIA

8-16 CELL LITHIUM BATTERY MANAGEMENT SYSTEM

Ensure that all wiring is secured so it will not become damaged from vibration or abrasion. 
Small fuses (~1A) may be used to protect wiring, best installed close to each cell terminal. 
Device power is always taken from terminal B+. To provide power to the BMS, simply add 
a short jumper wire from your most positive cell terminal to B+. (You can optionally run a 
dedicated wire from battery positive to B+ to avoid voltage measurement errors on your most 
positive cell, though it is usually only a few millivolts.) An example wiring diagram for 14 
cells is shown below.

 

Relay outputs are floating / isolated, and have a maximum rating of 70V and 1A continuous. 
In installations with a single “battery enable” relay, the LV and HV relays may be wired in 
series  such  that  either  an  over-voltage  or  under-voltage  condition  will  open  the  relay  to 
isolate the battery pack as shown on the following page.

Once your wiring is complete, press the power button on the top left of the case, and the 
status LED should come on. A green light indicates all cells are within correct voltage range, 
and both relay outputs will be closed circuit. A steady red light indicates one or more cells 
are over-voltage, and the HV Relay outputs will be open circuit. A blinking red light indicates 
one or more cells are under-voltage, and the LV Relay outputs will be open circuit. Green/
red flashing indicates an over-temperature shutdown.

Packs Smaller Than 12 Cells

Internally the BMS16 uses two voltage sampling 
chips which are connected to up to 8 cells each, 
one spanning terminals B– to 08 and the second 
from 08 to 16. These samplers require a minimum 
of 4 cells each for reliable operation, so for packs 
with  fewer  than  12  cells,  some  unusual  wiring 
is  required. The  most  positive  four  cells  should 
be connected between 08 to 12, with a jumper 
from 12 to B+ (since the BMS draws power from 
B+ to power itself). Then the remaining cells are 
connected from B– up, with a wire jumper from 
the  most  positive  terminal  in  this  group  up  to 
08. An example case for a 9-cell pack is shown 
right.

Protection Using a Single Contactor

It  is  possible  for  the  BMS  to  control  a  single 
contactor  to  protect  against  both  under-voltage 
and  over-voltage  conditions  concurrently.  To 
achieve this, the HV Relay and LV Relay terminal 
pairs  should  be  wired  in  series,  as  per  the 
diagram, right.

Note that in this configuration, if the BMS opens 
the main contactor due to an under-voltage cell 
for example, the battery pack will also be isolated 
from any charging sources so will be unable to 
charge (and correct the under-voltage condition) until the system is reset manually. For this 
reason it is important in this case that BMS intervention is an exceptional circumstance, and 
under normal operation chargers and loads will not cause any cells to exceed safe range. 

Current Shunt

The BMS16 may be supplied with either a 100A, 200A or 500A shunt. The shunt may be 
installed at either the negative end, positive end, or even somewhere in the middle of the 
battery pack. The shunt is connected via two wires to the associated terminals on the BMS16. 
For best performance, twisted pair wire is recommended. The sample wire from the anode 
/ positive side of the shunt (closest to the +ve terminal of the battery) should be connected 
to the left-hand terminal (as shown on the wiring diagram, left). By default, discharge amps 
are shown positive, though this can be reversed in settings if preferred. If your polarity seems 
to be reversed (e.g discharge current is causing SoC to increase), simply swap the two shunt 
wires at the BMS.

3

4

Reviews: