background image

ZERO EMISSION VEHICLES AUSTRALIA

4-12 CELL LITHIUM BATTERY MANAGEMENT SYSTEM

Balance voltage

2.00-4.50V, 

Dynamic 

or Off

The voltage threshold where shunt balancing will 
occur. Balancing should only be performed on 
cells which are higher than average, so typically 
set this to the average maximum charge voltage 
of each cell (i.e max charge voltage divided by 
number of cells).

Set  to  4.51V  for  dynamic  balance  voltage  or 
4.52V for Off.

BMS hysteresis

0.00-0.50V

Applies to Stationary Mode only.

 Adds hysteresis 

to  min/max  voltage  reset  thresholds,  so  that 
charge and load relays are not switched on and 
off  too  rapidly.  For  example,  after  an  under-
voltage  trip,  the  LV  relay  won’t  be  re-enabled 
until  the  cell  recovers  to  0.2V  above  Min 
Voltage.

BMS min temp

-41C to 100C The  minimum  allowable  temperature  for 

the  battery  pack.  If  a  temperature  below 
this  threshold  is  detected,  a  warning  will  be 
generated and charging will be disabled.

Set to -41C to disable (will show as “Off”)

BMS max temp

0-101C

The  maximum  allowable  temperature  for 
the  battery  pack.  If  a  temperature  above 
this  threshold  is  detected,  a  warning  will  be 
generated and chargers and loads will both be 
disabled.

Set to 101C to disable (will show as “Off”)

Charger voltage

0-70V

Applies to CAN bus integration with TC Chargers 
or SMA/Goodwe inverters only.

The maximum voltage that the BMS will instruct 
the charger/inverter to reach.

Charger current

0-100A

Applies to CAN bus integration with TC Chargers 
or SMA/Goodwe inverters only.

The maximum current that the BMS will instruct 
the charger/inverter to reach.

Stationary mode

No/Yes

Whether the BMS behaviour should be set for 
stationary  applications.  Please  see  “Stationary 
Mode” section for further explanation.

Reverse current display

No/Yes

By default, the BMS12i displays discharge amps 
as positive / charge amps negative. If preferred, 
you  can  reverse  the  display  so  that  discharge 
amps are negative / charge amps are positive.

Night Brightness

0-100%

Adjusts  the  brightness  of  the  LCD  display  in 
low  light  mode,  to  reduce  screen  glare  at 
night. Toggle between full brightness and night 
brightness by swiping a finger up/down.

Buzzer On

Yes/No

Selects whether the Monitor should sound the 
buzzer for alerts. (Safest to leave this on.)

Use Fahrenheit

Yes/No

Changes  display  of  temperature  units  to 
Fahrenheit instead of Celcius.

SoC Display

Percent or 

Amp-Hours

The battery State of Charge value displayed on 
the Monitor can either be shown as a percentage 
of full charge, or as the number of amp-hours 
remaining.

Stationary Mode

The BMS12i has two main modes of operation, either normal (for mobile / EV applications) 
or Stationary Mode (for off grid / backup battery type applications). In normal mode, if an 
under- or over-voltage is detected, the LV or HV output relay will be disabled respectively, 
and will remain off until the device is either power cycled or (more commonly) they are re-
enabled whenever the device wakes from sleep.

In Stationary mode, the outputs will automatically reset if the voltage recovers sufficiently. 
The BMS Hysteresis setting is used to adjust the amount that the voltage needs to recover 
before outputs are re-enabled. For example, if the HV output has been disabled due to an 
over-voltage cell, a Hysteresis setting of 0.2V will prevent the output from re-enabling until 
the high cell has fallen more than 0.2V below the Max Voltage setting.

Common settings for LiFePO4 cells are a 

Min Voltage

 setting of 2.50V, 

Max Voltage

 of 3.65V, 

and 

Hysteresis

 of 0.20V, giving a 2.5V-2.7V band for the LV Relay output and 3.45V-3.65V 

band for the HV Relay output. LiCo cells have a more linear charge curve so typically need a 
smaller hysteresis band around 0.10V, with a 

Min Voltage

 setting of 3.00V and a 

Max Voltage

 

setting of 4.2V.

9

10

Reviews: