ALARM SYSTEMS

ADDRESSABLE INTERFACE UNITS

ZIOU – ADDRESSABLE INPUT OUTPUT UNIT 

5

0

4

9

6

1

3

87

2

5

0

4

9

6

1

3

87

2

5

0

4

9

6

1

3

87

2

D

 

Connections & Address Setting 

 

The ZIOU has the following connections:-  
Loop IN + 
Loop IN – (2 connections) 
Loop OUT + 
Loop out – 
MON I/P (2 connections) 
AUX RELAY (3 connections, NO, CM, NC) 

 

Normally the loop cables will be connected one pair  of +/- to the IN terminals (use either IN- 
terminal), and the other pair of  cables to the OUT terminals. If the isolator needs to be 
PERMANENTLY bypassed, connect the – OUT to the spare –IN terminal. To temporarily bypass 
the isolator (eg for a DVM cable continuity check), fit a shorting link to position J1.  

 

The ZIOU is now addressed by 3 rotary switches, one for 100`s one for 10`s, one for units. Select 
an address between 1 & 126. (The picture shows 037) 

PCB Identification 

 
The same PCB is used for The 
ZIU (input only), ZIOU (Input 
with volt free relay output), and 
ZSCC (sounder circuit 
controller). Each PCB will have 
an Identification mark (tick or 
“X”) to show which model it is. 

Description 

 

The Zeta addressable Input Output Unit (ZIOU) is used to  
interface external equipment to any Zeta Analogue  
Addressable fire alarm system. It has a switch monitoring 
input with a 47k end of line resistor, and a Volt Free SELV 
relay output. 

 

The unit has a built in loop short circuit isolator to help  
keep the unit operational in the event of a problem on the  
addressable loop wiring. 

 

It has 3 indication LEDs on the front of the unit. One for 
Alarm, one for local fault and one for addressable loop fault (Isolator active). 