background image

 

 

 

DOC: GLT.MAN-126 

 

 ISSUE: 

www.gltexports.com  

DATE: 

14/4/08

 

 

 

ALARM SYSTEMS

ADDRESSABLE INTERFACE UNITS

ZIOU – ADDRESSABLE INPUT OUTPUT UNIT 

 
 
 
                          

Technical Data  

 

OPERATING VOLTAGE 

17 – 33V DC 

QUIESCENT CURRENT 

900uA 

ALARM CURRENT 

10.6mA 

FAULT CURRENT 

2.8mA 

ISOLATING CURRENT 

7.3mA 

INPUT END OF LINE 

47K 

DEVICE NORMAL RESISTANCE (RETURN VALUE 16) 

10K to 75K 

DEVICE OPEN CCT FAULT RESISTANCE (RETURN VALUE 4) 

85K to open circuit 

DEVICE ALARM RESISTANCE (RETURN VALUE 64) 

0K to 5K 

RELAY RATING 

1 AMP SELV ONLY 

OPERATING TEMPERATURE 

0

o

C to 50

o

MAX HUMIDITY 

95% RH Non Condensing 

IP RATING 

IP43 

SIZE 

127 x 88 x 59 mm

 

WEIGHT 

220g 

Short Circuit Isolator Specification 

 

MAXIMUM LINE VOLTAGE 

33V DC 

MINIMUM LINE VOLTAGE (NON ISOLATING) 

17V DC 

MAXIMUM RATED CONTINUOUS CURRENT 

1 Amp 

MAXIMUM RATED SWITCHING CURRENT 

3 Amp 

MAXIMUM LEAKAGE CURRENT (ISOLATING) 

0.7 mA 

MAXIMUM SERIES IMPEDENCE 

0.2 Ohm 

ISOLATION VOLTAGE 

15.6V +/- 0.5V 

ISOLATION RESPONSE TIME 

25 us to 300 us 

RECONNECTION VOLTAGE 

18.5V +/- 0.5V 

RECONNECTION TIME 

UP TO 2 SEC 

 

Troubleshooting 

 

DEVICE NOT SEEN BY PANEL 

CHECK ADDRESS SETTING 
CHECK WIRING TO DEVICE  (FOR CONTINUITY & POLARITY) 
CHECK FOR LOOP VOLTAGE AT  & - TERMINALS 

DEVICE REPORTS A FAULT (ANALOGUE VALUE 4) 

CHECK WIRING FROM DEVICE TO MONITORED CONTACT 
CHECK FOR CORRECT END OF LINE 

DEVICE REPORTS AN ALARM (ANALOGUE VALUE 64) 

CHECK IF MONITORED CONTACTS ARE OPERATING CORECTLY 
CHECK FOR SHORT CIRCUIT ON WIRING 
CHECK THAT A NORMALLY CLOSED CONTACT IS 

NOT

 USED 

ANALOGUE VALUE UNSTABLE 

CHECK FOR DOUBLE ADDRESS FAULTS 
CHECK FOR LOOP DATA CORRUPTION WITH LOOP TEST TOOL 

LOOP FAULT (ISOLATING) LED ON 

CHECK FOR SHORT CIRCUIT ON LOOP 
CHECK FOR WRONG POLARITY CONNECTION TO LOOP DEVICES 
CHECK FOR TOO MANY DEVICES BETWEEN ISOLATORS 

RELAY NOT OPERATING IN ALARM 

PREMIER AL: - CHECK RELAY HAS BEEN PROGRAMMED 
CORRECTLY 
PREMIER AD:- RELAY MAY BE CONFIGURED AS ZONAL IF  
DETECTORS ARE ADDRESSED IN THE SAME ZONE 
CHECK RELAY RATING HAS NOT BEEN EXCEEDED 
DISCONNECT LOAD & CHECK THAT RELAY SWITCHES 

Protocol usage 

 

The ZIOU addressable interface unit`s relay is controlled by command bit 0 from the control panel. It`s operation will depend on whether the 
control panel has pre-configured outputs (EG Simplicity), or programmable outputs (EG Premier AL)  
 
All it`s indication LEDs are under its own control. 
 
In the event of an alarm, it will set input bit 0 to an active condition, as well as setting it’s analogue value to 64 to indicate it’s activation.

Other information 

 

Like all electronic equipment, at the end of it`s working life this unit should not be disposed of in a refuse bin.  
It should be taken to a local reprocessing site as per the guidelines of the WEEE directive, for correct disposal. 
 
Input/Output section designed to EN54-18:2005 
Short Circuit Isolator section designed to EN54-17:2005 
 

Reviews: