Addressing the System.

  

The ID2 divides the loop addresses into zones and Ids. The panel translates the address into a zone 

and ID. Each zone starts with ID1, in order to simplify the addressing. 

To assist with setting the dip switches, there is a free app available for download on the APP Store 

for iOS, or Google Play for Android 

 

 

 

 

 

Once all the installation has been checked for any cable faults, and all the devices have been 

addressed and fitted, connect the loop or radial circuits and turn the panel on. 

CONNECTING MAINS POWER 

CONNECTING THE BATTERIES 

 

 

The panel should be connected to 220-240V 
AC by a 3A rated spur to the fuse box with 
1mm

to 2.5mm

3-core cable.  

 
Nothing else should be connected to this 
supply. The cable should be fire resistant. 

Although there are many sizes of suitable battery, 
the sizes we usually recommend for the ID2 are 12V 
7Ah, 
 
The two batteries are wired in series to give 24 
Volts. 

 

 