Zeta ID2/8 Quick Start Manual Download Page 4

Doc: GLT-211-7-3 

Iss: 2.0 

Date 03/08/2016 

 

Configuring the panel. 
 

The basic steps to configuring the panel are shown below:- 
 

Step 

Function 

How to do 

Set the device dip switches 

Use the smartphone App, remembering that devices set as zone 1 must 
be connected to zone 1 circuit etc 

Go To Engineer Screen 

Enter engineer code on the panel (enter then 369) 
Enter again for menu 
Select 4 for engineer 

Learn the devices onto the zone  
(learn 1 zone at a time, correcting any 
configuration errors as you go along) 

Select 1 for configure zone 
Select 2 for configure now 
Wait until panel finishes 
Check zone contents to confirm it matches what is fitted 
Repeat for each zone 

Enter Device labels (Optional) 

Go to Engineer screen (see 2 above) 
Press 3 for ID device 
Use Prev/Next to select device to label. 
Press enter to bring up cursor 
Enter text using keypad. 
Press enter to save text 
Use Prev/Next to edit other devices as required 

Enter Panel Name (Optional) 

Go to Engineer screen (see 2 above) 
Press 2 for Panel/Zone text 
Select x for Panel 
Enter First line of text text using keypad. 
Press enter to save text 
Enter second line of text if required 
Press enter to save text 
Use Prev/Next to edit other zones as required 

Enter Zone label (Optional) 

Go to Engineer screen (see 2 above) 
Press 2 for Panel/Zone text 
Select x for zone 
Use Prev/Next to select Zone. 
Press enter to bring up cursor 
Enter text using keypad. 
Press enter to save text 
Use Prev/Next to edit other zones as required 

 

Testing / Commissioning. 
 

When testing the system for the first time it is recommended the following steps are taken. 
 

1.

 

Test each device to make sure it triggers the control panel in a fire condition, e.g. panel 
shows the correct information and also starts the sounders. 
 

2.

 

Test each device to make sure it triggers the control panel in a fault condition, e.g. detector 
removal, loop open circuit. Note that this can take up to 30 seconds to report. 

 

3.

 

When testing both fire and fault make sure the text label that has been entered is correct 
and matches the device you are testing. (If a text label has been entered). 

 

4.

 

Check the power supply triggers a fault when the mains power is disconnected and also 
when the batteries are removed. 