Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
43
SCM-MIM
Multi Input Module
48
73
SCM-ZMM
Zone Monitor Module
62
97
SCM-RM
Multi Relay Module
28
116
SCM-ACM
Alarm Circuit Module
32
32+ alarm load
SCM-NM
Network Module - RS485
SCM-PM
RS232 Module (Printer Driver)
37
37**
MKII-AOP
MKII Addressable Optical Smoke Detector
0.5
5
MKII-AOH
MKII Addressable Combined Optical Smoke & Heat (A1R)
Detector
0.5
5
MKII-AHF
MKII Addressable Fixed Heat Only A2S Detector
0.5
5
MKII-AHF/CS90
MKII Addressable Fixed Heat Only CS Detector
0.5
5
MKII-AHR
MKII Addressable RoR & Fixed Heat Detector A1R Detector
0.5
5
MKII-AOPI
MKII Addressable Optical Smoke Detector With Built-In Isolator 0.5
5
MKII-AOHI
MKII Addressable Combined Optical Smoke & Heat (A1R)
Detector With Built-In Isolator
0.5
5
MKII-AHFI
MKII Addressable Fixed Heat Only A2S Detector With Built-In
Isolator
0.5
5
MKII-AHFI/ CS90
MKII Addressable Fixed Heat Only CS Detector With Built-In
Isolator
0.5
5
MKII-AHRI
MKII Addressable Rate of Rise & Fixed Heat Detector A1R
Detector With Built-In Isolator
0.5
5
MKII-ARL
MKII Addressable Remote LED Indicator
0.5
5
ZT-CP3/AD
Addressable CP3 Manual Call Point
0.45
2.3
ZAI-MI
MKII Addressable Input Module with S/C Isolator
1
3.6
ZAIO-MI
MKII Addressable Input/Output Module with S/C
1
2
ZASC-MI
MKII Addressable Sounder Circuit Controller with S/C Isolator
0.6
0.8
ZAZM-MI
MKII Addressable Zone Monitoring Unit with S/C Isolator
3.5
13.2
ZAIO/230
MKII Addressable Mains switching Input/Output Module
1.5
4.6
SMM/B
Special Mini Modules (White) - Beam Detector
1.1
12
MKII-SSB
MKII Sandwich Sounder (No Address Required)
0.65
5.5
MKII-AXT
MKII Addressable Xtratone Wall Sounder
1.5
5.4
MKII-AXTB
MKII Addressable Xtratone Combined Sounder Beacon
1.5
19-44***
ZRAP
MKII Addressable Raptor Weatherproof Sounder
1.5
5.4
ZRAPB
MKII Addressable Raptor Weatherproof Sounder Beacon
1.5
19-44***
MKII-OP
MKII Conventional Fyreye Optical Smoke Detector
0.07
35-45****
MKII-HR
MKII Conventional Fyreye ROR Heat Detector
0.07
35-45****
MKII-HF
MKII Conventional Fyreye Fixed Heat Detector
0.07
35-45****
MKII-HF-CS90
MKII Conventional Fyreye Fixed Heat (CS) Detector
0.07
35-45****
MKII-OH
MKII Conventional Fyreye Opto-Heat Detector
0.07
35-45****
MKII-RL
MKII Conventional Remote LED Indicator
0.45
2.1****
ZXT
Xtratone Conventional Wall Sounder
0
10
ZXTB
Xtratone Conventional Combined Wall Sounder Beacon
0
60-70***
ZRP
Conventional Raptor Sounder
0
10
ZRPB
Conventional Raptor Sounder Beacon
0
60-70***
*Loop device current and alarm current not included. On batteries use 1.5x current to allow for DC-DC step up voltage
**Current for printing out alarm message not included
***Depends on flasher intensity setting
****For use with either SCM-ZMM, or the MKII-ZAZM loop powered module
Appendix C: LOOP DEVICE ADDRESS SETTING
Soft Addressing
(with handheld programming tool)
The MKII Handheld Programmer is designed to complement all MKII devices and to assist the commissioning engineer on site. The unit
will softly address all devices without using the incorporated dip-switch on the field devices.