Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
25
Compatible Warning Devices
Alarm Circuit Devices
ZXT
Xtratone Conventional Wall Sounder
ZXTB
Xtratone Conventional Combined Wall Sounder Beacon
ZRP
Conventional Raptor Sounder
ZRPB
Conventional Raptor Sounder Beacon
Maximum Warning Devices per Circuit
Some of the above warning devices have selectable settings for sound and beacon output. Please refer to the device manuals to
calculate the maximum number allowed on each alarm circuit.
SCM-MIM Field Wiring Connections
Wiring Recommendations for Input Circuits
(SCM-MIM)
Wire Gauge (AWG)
Maximum Wiring Run (Metres)
22
910
20
1450
18
2300
SCM-MIM Specifications
Multi Input Module (SCM-MIM)
Circuit Voltage
24VDC Nominal (16V
–
24.5V with EOL fitted)
Wiring Class
6 x Class B circuits
Input Maximum Line Impedance
10Ω
End of Line Resistor
4K7Ω
Recommended cable sizes
22 AWG to 18 AWG (0.3mm
2
to 0.8mm
2
)
Alarm Trigger Resistor
1KΩ
RECOMMENDED CABLE:
Cable should be BS approved FPL, FPLR, FPLP or equivalent.