Panel
Charger Boost
Voltage
Charger Float
Voltage
PSU Cage Size
Max Charger Current
Max Battery Size
Fuse
Installed
SMART6
29.5V DC
27.6V DC
400W
1.1A
2 x 12V, 14 Ah
5A
SMART10
29.5V DC
27.6V DC
400W
2.2A
2 x 12V, 38 Ah
8A
SMART26
29.5V DC
27.6V DC
400W
2.2A
2 x 12V, 38 Ah
15A
Securing the batteries
The SMART Connect Multi-loop has been designed so that the batteries are secured in the panel with Velcro strips.