PREMIER QUATRO USER MANUAL, MAINTENANCE GUIDE & LOG BOOK (Fyreye MKII)
#Doc No. GLT-215-7-2
PAGE 9
Issue: 1.08 Author: TE/NJ Date: 26/05/2017
5.4 TURNING ON THE ALARM SOUNDERS FROM THE FACP (TO EVACUATE THE BUILDING)
If a user comes across a fire in the protected building, the alarm can also be raised by operating the START / STOP
SOUNDERS button on the front of the Fire Alarm Control Panel.
With the control key in CONTROLS ENABLED position, momentarily pressing the Start/Stop will cause the Alarm sounders
to sound.
Pressing the START/STOP SOUNDERS button again will Silence the Alarm Sounders.
Note: If ALL of the Alarm Sounders have been disabled, pressing the STOP/START BUTTON will have
NO
effect.
5.5 RESETTING THE PANEL
Check the cause of the alarm activation. If the cause of the alarm was an activated call point, reset it (if a resettable type),
or fit a new glass element (if a glass type). If the cause of the alarm was by detector activation the smoke (or steam or
other stimulus) will have to be cleared from the room before the panel can be reset. Reset the panel by pressing the reset
button after the sounders and panel buzzer have been silenced.
If the call point is still active, or the detector is still smoky, this will cause another alarm straight after the panel is reset,
and the alarm sounders will start again.