PREMIER POWER PACK INSTRUCTION MANUAL
GLT.MAN-138
PAGE 8
Issue: 1.13 27/7/2012 N.R.P.J.
CONNECTING THE MAINS & BATTERY
The Power Supply should be connected to 230V AC by a 3A rated spur to the fuse box with 1.0mm
2
to 2.5mm
2
3-
core cable. Nothing else should be connected to this supply
The mains input is to be connected to the PSU Cage. The Live, Earth and Neutral connections are marked on the
switch mode cage.
The incoming mains cable should be kept separate from the other cables to help minimise mains interference.
The two batteries are wired in
series
.
The
+ve
of one battery is connected to the
red
battery charger lead.
The
–ve
of the other battery is connected to the
black
battery charger lead.
The –ve of the first battery is connected to the +ve of the second battery using the FUSED link wire supplied.
24V DC Outputs
Fault Relay