INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT-201-7-2
PAGE 5
Issue: 1.2 Authorised: Date: 27/3/2012
4.3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING
Use the table below to determine the condition of the panel.
LEDs LIT
LED CONDITION
PANEL STATUS
POWER
CONSTANT GREEN
The panel is supplied with power, and has no faults / fires (System Normal)
GEN FLT
ONLY
FLASHING YELLOW
GEN FLT &
SUPPLY FLT
FLASHING YELLOW
FLASHING YELLOW
There is a problem with either the mains supply or the battery backup.
(Consult Installation manual for details of flash meanings)
GEN FLT &
EARTH FLT
FLASHING YELLOW
CONSTANT YELLOW
There is a wiring problem. One of the cables is touching the earth screen.
GEN FLT &
ZONAL FLT
CONSTANT YELLOW
FLASHING YELLOW
There is an open circuit fault in the wiring of the zone indicated.
GEN FLT &
ZONAL FLT
GEN S/C
FLASHING YELLOW
FLASHING YELLOW
FLASHING YELLOW
There is a short circuit fault in the wiring of the zone indicated.
GEN FLT &
SND FLT
FLASHING YELLOW
FLASHING YELLOW
There is an open circuit fault in the wiring of one or both of the sounder
circuits
GEN FLT &
SND FLT
GEN S/C
FLASHING YELLOW
FLASHING YELLOW
FLASHING YELLOW
There is a short circuit fault in the wiring of one or both of the sounder
circuits
GEN FLT &
SYSTEM FLT
CONSTANT YELLOW
CONSTANT YELLOW
A processor fault has occurred. To reset, If problem persists, consult your
dealer.
GEN FIRE
ONLY
NO LED
A manual evacuation has occurred.
The sounders will be active.
GEN FIRE &
ZONE FIRE
CONSTANT RED
CONSTANT RED
A fire has occurred in the zone indicated.
The sounders will be active.
GEN FIRE &
ZONE FIRE &
GEN DISABLE
& DEL
CONSTANT RED
CONSTANT RED
CONSTANT YELLOW
CONSTANT YELLOW
A fire has occurred in the zone indicated.
The sounders have a delay set, and will become active after the
programmed delay. To override the display, press override sounder delay.
GEN DISABLE
FLASHING YELLOW
(FAST
– 4 HZ)
The panel is ready for selecting disable or test mode
GEN DISABLE
FLASHING YELLOW
(SLOW
– 0.5 HZ)
The panel is in SELECT DISABLEMENT MODE
GEN DISABLE
ZONE DISABLE
FLASHING YELLOW
(SLOW
– 0.5 HZ)
The user is scrolling through zones to select which one to disable/or user
has just enabled the zone.
GEN DISABLE
ZONE DISABLE
CONSTANT YELLOW
CONSTANT YELLOW
The indicated zone is disabled.
GEN DISABLE
DEL
CONSTANT YELLOW
CONSTANT YELLOW
The Sounders are delayed by the amount set on the rotary switch.
GEN TEST
ZONE DISABLE
FLASHING YELLOW
FLASHING YELLOW
(VERY SLOW
– 0.25 HZ)
The indicated zone is in Test Mode.
4.4 CHECKING THE PANELS INDICATION LEDS
To test panel LED’s press
button. All the LEDs on the front panel will light, and the panel’s internal
buzzer will also sound. This function is available at
Level 1
.