Zeta Alarm Systems Infinite 8 User Manual, Maintenance Manual & Log Book Download Page 3

INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT-201-7-2 

 

PAGE 2

 

Issue: 1.2      Authorised:         Date: 27/3/2012 

 

1. FIRE ALARM CONTROL PANEL SAFETY ISSUES 

 

There is no need to open this fire alarm during normal operation. Any work carried out on this system must be 
performed by a competent person who is familiar with this type of system.  

 

This  equipment  will  operate  safely  provided  it  has  been  installed  correctly  in  compliance  with  the  Installation 
Manual. 

 

It  is  recommended  that  the  system  is  serviced  frequently.  It  is  customary  to  arrange  a  regular  maintenance 
contract  with  a  competent  organisation.  (Ask  the  installation  company  for  recommendations).  The  system 
needs a thorough maintenance check annually at the very minimum.  

 

If  any  part  of  this  Fire  Alarm  Control  Panel  becomes  damaged,  contact  the  company  responsible  for  system 
maintenance to arrange repair / replacement. 
 

C E   

European Union Directives Conformance Statement 

This product has been manufactured in conformance with the requirements of all 
applicable  EU  Council  Directives.    The  Declaration  of  Conformance  for  this 
product is located at the following Address:  GLT Exports Ltd, 72-78 Morfa Road, 
Hafod, Swansea, SA1 2EN, United Kingdom 

 

 

2. THE PURPOSE OF A FIRE ALARM SYSTEM 

 

A Fire Alarm System is used to provide an early warning of a fire, so that the property can be evacuated and 
the  fire  extinguished  if  it  can  be  safely  tackled,  or  the  local  fire  brigade  called,  according  to  the  company 
evacuation procedure. 

 

Alarms can come from Smoke or Heat Detectors, or manually be a person operating a Manual Call Point. 

 

Split  the  system  into  Zones,  each  covering  a  different  area  of  a  building.  This  will  indicate  which  area  of  the 
system is giving the alarm (or fault). 

 

During an alarm, the panel will start its sounders, and indicate which zone has the fire. It will also activate its 
auxiliary relay. 
 

Fault Monitoring

 

 

All  circuits  must  be  checked  for  line  integrity.  If  a  part  of  the  system  has  a  problem  which  may  affect  its 
operation, a fault warning must be given by the fire alarm panel (LED & buzzer indication). The fault relay will 
also activate. 

 
Disablements

 

 

An  engineer  may  be  required  to  work  on  part  of  a  system,  while  the  system  is  still  active  (e.g.  extending  a 
detection zone). During such circumstances, it would be advisable to disable that zone, so that it will not give 
false  alarms.  Similarly  you  may  wish  to  disable  a  zone  that  has  a  fault  that  has  not  been  fixed,  or  a  zone 
covering  an  area  with  a  temporary  unusual  environment,  such  as  an  area  which  is  dusty  because  of 
construction work etc. 

 
Delays

 

 

In public places, it may be desirable to delay the activation of an alarm until the responsible person has verified 
the  cause  of  the  alarm.  (This  would  avoid  a  panic  evacuation  caused  by  a  smoky  room,  or  a  maliciously 
activated call point.) On verification of the alarm, the sounders can be started by pressing the override button, 
or  the  panel  can  be  reset  in  the  case  of  a  false  alarm.  If  a  delay  has  been  set,  it  must  be  recorded  on  the 
system configuration chart at the back of this manual. 

 

Power Supply Equipment- General Description. 

 

The INFINITY 8 FACP has an integral linear power supply capable of supplying 1.2 amps in total. It contains a 
current limited output for charging sealed lead acid batteries (3.4 Ah maximum). The PSE is monitored for main 
supply failure, the battery not taking a charge, low battery voltage and resistance. If the battery voltage drops 
below approximately 20VDC (a fault condition), the battery charging current will be turned off, thus stopping 
charging. This PSE is only capable of supplying power to the CIE, and is not designed for any other use. 

 
 

 

 

Summary of Contents for Infinite 8

Page 1: ...INFINITY 8 USER MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT 201 7 2 Issue 1 2 Authorised Date 27 3 2012 FIRE ALARM CONTROL PANEL USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Page 2: ...ACP I E TO EVACUATE THE BUILDING 6 5 5 RESETTING THE PANEL 6 6 THE FAULT CONDITION 7 6 1 DIFFERENT TYPES OF FAULT 7 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS 8 7 DISABLEMENTS 9 7 1 REASONS FOR DISABL...

Page 3: ...arm or fault During an alarm the panel will start its sounders and indicate which zone has the fire It will also activate its auxiliary relay Fault Monitoring All circuits must be checked for line int...

Page 4: ...orded with updated drawings operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the Infinity 8 Range of Fire Alarm Panels...

Page 5: ...g the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid unauthorised changes to critical parts of the Fire Alarm System controls such as silencin...

Page 6: ...er circuits GEN FLT SYSTEM FLT CONSTANTYELLOW CONSTANTYELLOW A processor fault has occurred To reset If problem persists consult your dealer GEN FIRE ONLY NOLED A manual evacuation has occurred The so...

Page 7: ...ily pressing the button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit The Auxiliary Fire relay will remain active The Pane...

Page 8: ...em on a Zone or detector has been removed from its base It should be noted that any alarms raised on the fault zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been...

Page 9: ...ults are cleared the General Fault light will go out and the Panel s Internal Sounder will be silent if not already muted System Fault The System Fault LED and Gen fault lights when the Panel s micro...

Page 10: ...ot be disabled External sounders can also be disabled as could be required in certain conditions 7 2 TO DISABLE A ZONE AND OR EXTERNAL SOUNDERS 1 Enter the access code default 1245 and press 2 Hold th...

Page 11: ...efault 1245 Press button Press button again to deactivate sounder delay 8 3 HOW THE PANEL INDICATES SOUNDER DELAY If a Delay has been programmed into the Panel the General Disablement DEL AY LEDs will...

Page 12: ...be left in test mode if the user needs to access another function e g disable 9 2 TO PROGRAMME ZONE IN TEST 1 Enter access code and press 2 Hold button for 3 seconds 3 Select the zone you want to go...

Page 13: ...Circuits OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User needs t...

Page 14: ...ng work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that...

Page 15: ...MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT 201 7 2 PAGE 14 Issue 1 2 Authorised Date 27 3 2012 MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK...

Page 16: ...d Document No GLT 201 7 2 PAGE 15 Issue 1 2 Authorised Date 27 3 2012 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDIN...

Page 17: ...BOOK Approved Document No GLT 201 7 2 PAGE 16 Issue 1 2 Authorised Date 27 3 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KN...

Page 18: ...ll points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for complian...

Page 19: ...h I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variatio...

Page 20: ...uidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commiss...

Page 21: ...ed below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of lia...

Page 22: ...e clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with th...

Page 23: ...y this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre oper...