INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT-201-7-2
Issue: 1.2 Authorised: Date: 27/3/2012
FIRE ALARM CONTROL PANEL
USER MANUAL, MAINTENANCE
GUIDE & LOG BOOK
Page 1: ...INFINITY 8 USER MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT 201 7 2 Issue 1 2 Authorised Date 27 3 2012 FIRE ALARM CONTROL PANEL USER MANUAL MAINTENANCE GUIDE LOG BOOK...
Page 2: ...ACP I E TO EVACUATE THE BUILDING 6 5 5 RESETTING THE PANEL 6 6 THE FAULT CONDITION 7 6 1 DIFFERENT TYPES OF FAULT 7 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS 8 7 DISABLEMENTS 9 7 1 REASONS FOR DISABL...
Page 3: ...arm or fault During an alarm the panel will start its sounders and indicate which zone has the fire It will also activate its auxiliary relay Fault Monitoring All circuits must be checked for line int...
Page 4: ...orded with updated drawings operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the Infinity 8 Range of Fire Alarm Panels...
Page 5: ...g the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid unauthorised changes to critical parts of the Fire Alarm System controls such as silencin...
Page 6: ...er circuits GEN FLT SYSTEM FLT CONSTANTYELLOW CONSTANTYELLOW A processor fault has occurred To reset If problem persists consult your dealer GEN FIRE ONLY NOLED A manual evacuation has occurred The so...
Page 7: ...ily pressing the button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit The Auxiliary Fire relay will remain active The Pane...
Page 8: ...em on a Zone or detector has been removed from its base It should be noted that any alarms raised on the fault zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been...
Page 9: ...ults are cleared the General Fault light will go out and the Panel s Internal Sounder will be silent if not already muted System Fault The System Fault LED and Gen fault lights when the Panel s micro...
Page 10: ...ot be disabled External sounders can also be disabled as could be required in certain conditions 7 2 TO DISABLE A ZONE AND OR EXTERNAL SOUNDERS 1 Enter the access code default 1245 and press 2 Hold th...
Page 11: ...efault 1245 Press button Press button again to deactivate sounder delay 8 3 HOW THE PANEL INDICATES SOUNDER DELAY If a Delay has been programmed into the Panel the General Disablement DEL AY LEDs will...
Page 12: ...be left in test mode if the user needs to access another function e g disable 9 2 TO PROGRAMME ZONE IN TEST 1 Enter access code and press 2 Hold button for 3 seconds 3 Select the zone you want to go...
Page 13: ...Circuits OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User needs t...
Page 14: ...ng work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that...
Page 15: ...MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT 201 7 2 PAGE 14 Issue 1 2 Authorised Date 27 3 2012 MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK...
Page 16: ...d Document No GLT 201 7 2 PAGE 15 Issue 1 2 Authorised Date 27 3 2012 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDIN...
Page 17: ...BOOK Approved Document No GLT 201 7 2 PAGE 16 Issue 1 2 Authorised Date 27 3 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KN...
Page 18: ...ll points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for complian...
Page 19: ...h I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variatio...
Page 20: ...uidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commiss...
Page 21: ...ed below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of lia...
Page 22: ...e clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with th...
Page 23: ...y this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre oper...