EDA-R6000 Installation Manual 

 

Page 

2

 of 6                                      Ref: EDA_R6000_install_V107.doc    

 

 

 

 

 

 

Electro-Detectors

 

Sensitivity 

The sensitivity can be adjusted by the control panel to the following settings. 
High:   

0.08dB/m   (1.8%)  

Medium: 

0.12dB/m   (2.7%)    Always use for EN54 Part 7 detectors 

Low: 

 

0.20dB/m   (4.4%)  

 

Alarm Verify 

The time period, in seconds, that a detector remains in alarm before sending an alarm signal. 
Range: 1 to 20 seconds 
The recommended value which conforms with third party type approval tests is 2 Seconds 

 
Volume 

The  volume  of  the  unit,  when  it  is  sounding,  can  be  set  inside  the  unit.  We  would  recommend  that  this  is  left  as  its 
default maximum setting which conforms to EN54-3 as tested. Care should be exercised when changing volume levels 
as the appropriate sections of BS5839 should be considered. The  type approved volume level quoted was measured at 
the maximum volume setting. 
High 

 

Maximum  

 

80dB at 1m* 

Medium 

 

 

 

75dB at 1m   

Low 

 

 

 

 

65dB at 1m   

Quiet   

Very Low Level 

35dB at 1m  

Off 

 

No Sound 

 

0dB 

 

(*type  tested  to  this  volume.  This  was  the  minimum  volume  recorded  in  all  directions.  Depending  on  orientation  a  maximum  of  90dB  can  be 
achieved) 

 
Area 1 and Area 2 

In  order  to  allow  for  sector  sounding,  a  sounder  unit  can  be  programmed  in  to  a  logical  area  or  group,  eg  1

st

  floor. 

Usually the systems are set up as all out evacuate systems which ignores this setting and so does not matter what it is set 
at. They default to 101 and 101 and it is recommended that they be left as this unless special cause and effects are being 
used. The panel can be programmed so that different areas / groups of sounders can be operated. The sounders can be 
put  into  two  separate  groups.  If  a  panel  instructs  the  system  to  sound  a  particular  group  then  only  these  sounders 
programmed  to  that  group  will  sound.  If  the  areas  are  left  as  area  0  then  whatever  the  panel  is  programmed  to  then 
sounders programmed into area 0 will always sound.

  

 
Output Timeout 

This  controls  how  long  the unit will sound before automatically silencing. Once automatically silenced the panel will 
remain  indicating  the  alarm  but  the  unit  will  be  silenced.  Should  another  alarm  condition  occur  then  the  unit  will 
resound. This can be set in multiples of 30 minutes from 0 to 900 minutes. Setting the value at 0 will allow the unit to 
sound continuously. The default value is 30 minutes. 

 