background image

 

EDA-R6000 Installation Manual 

 

Page 

3

 of 6                                      Ref: EDA_R6000_install_V107.doc    

 

 

 

 

 

 

Electro-Detectors

 

Sounder Tone List 
 

Two tones are available. A swept tone that should be used as a general evacuate tone and a single frequency tone that is 
pulsed and used for an alert signal.  
 
To achieve EN54 Part 3 compliance the swept tone must be used with the maximum (High) volume setting. 
 
When programming the panel, for each device that can set the system into alarm, a set of cause and effects can be 
programmed to determine how the sounders operate. The options are detailed below. The system defaults to sounder 
tone number 0 and has been type approved to this. Other options have not been approved. Four user defined tones can 
be added to the system. 
The swept tone sweeps from 1056Hz to 918Hz in 500mS 
The pulsed single frequency operates on a 50% duty cycle and is on for 1 second. 
 

Sounder  
Tone  
Number 

Tone Name 

Tone Description 

Swept 

Swept Tone 

Pulsed 

Pulsed 1s on 1s off 

Swept 

Swept Tone 

Pulsed 

Pulsed 1s on 1s off 

Swept 

Swept Tone 

Pulsed 

Pulsed 1s on 1s off 

Swept 

Swept Tone 

Pulsed 

Pulsed 1s on 1s off 

No Tone 

No Tone 

No Tone 

No Tone 

10 

No Tone 

No Tone 

11 

No Tone 

No Tone 

12 

User Tone A 

User Tone A 

13 

User Tone B 

User Tone B 

14 

User Tone C 

User Tone C 

15 

User Tone D 

User Tone D 

Reviews: