INSTALLATION
MOUNT HEIGHTS
DUCTING
10"
36"
96"
Min 24"-Max 32"
Minimum mount height between range top to
hood bottom should be no less than 24".
Maximum mount height should be no higher
than 32".
It is important to install the hood at the
proper mounting height. Hoods mounted too
low could result in heat damage and fire haz-
ard; while hoods mounted too high will be
hard to reach and will loose its performance
and efficiency.
If available, also refer range manufacturer's
height clearance requirements and recom-
mended hood mounting height above range.
A minimum of 6" round or 3-1/4” x 10"rectangular
duct must be used to maintain maximum air flow
efficiency.
Always use rigid type metal ducts only.
Flexible ducts could restrict air flow by up to 50%.
Also use calculation (on right) to compute total
available duct run when using elbows, transitions
and caps.
ALWAYS, when possible, reduce the number or
transitions and turns. If long duct run is required,
increase duct size from 6" to 7 or 8". If a reducer
is used, install a long reducer instead of a pancake
reducer. Reduce duct size as far away from open-
ing as possible.
If turns or transitions are required:
Install as far away from opening and as far
apart, between 2, as possible.
Duct Run Calculation:
Maximum run
6" or 3-1/4” x 10" duct
Deduct:
each 90 Elbow used
each 45 elbow used
each 6" to 3/14 x 10"
transition used
each 3/14 x 10" to 6"
each 3/14 x 10" to 6"
transition used
Side Wall Cap w/ damper
Roof Cap
100 FT
15 FT
9 FT
1 FT
5 FT
30 FT
30 FT
e.g.- 1 roof cap, 2x90 elbows, 1 x 45 elbow used:
=30' + 30' + 9' =69' used, 31' available for straight duct runs.
Models: AK7000, AK7036, AK7042
Page 1
Minimum Duct Size:
Round:
6" minimum
Rectangular:
3-1/4” x 10”
INSTALLATION
DUCTING
NEVER exhaust air or terminate duct work into spaces between walls, crawl spaces, ceiling,attics or
garages. All exhaust must be ducted to the outside.
Use metal ductwork only.
Fasten all connections with sheet metal screws and tape all joints w/ certified Silver Tape or Duct Tape.
Some Ducting Options:
WARNING FIRE HAZARD
Side wall cap
w/ gravity damper
Side wall cap
w/ gravity damper
Soffit or crawl space
Roof Pitch w/
Flashing & Cap
Rear Ducting
Models: AK7000, AK7036, AK7042
Page 2