Square TMD
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
50
70
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 -
670760.00
[T1] Temperature Source 2
External Sensor Temperature
71
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 -
670760.00
[T1] Effective Temperature
Effective Control Temperature
72
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[T1] Special Mode
1-byte HVAC Mode
73
1 Bit
I
C - - W -
DPT_Trigger
0/1
[T1] Special Mode: comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[T1] Special Mode: comfort
0 = Off; 1 = On
74
1 Bit
I
C - - W -
DPT_Trigger
0/1
[T1] Special Mode: standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[T1] Special Mode: standby
0 = Off; 1 = On
75
1 Bit
I
C - - W -
DPT_Trigger
0/1
[T1] Special Mode: economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[T1] Special Mode: economy
0 = Off; 1 = On
76
1 Bit
I
C - - W -
DPT_Trigger
0/1
[T1] Special Mode: protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[T1] Special Mode: protection
0 = Off; 1 = On
77
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[T1] Window Status (input)
0 = Closed; 1 = Open
78
1 Bit
I
C - - W -
DPT_Trigger
0/1
[T1] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
79
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[T1] Special Mode Status
1-byte HVAC Mode
80
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 -
670760.00
[T1] Setpoint
Thermostat Setpoint Input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 -
670760.00
[T1] Basic Setpoint
Reference Setpoint
81
1 Bit
I
C - - W -
DPT_Step
0/1
[T1] Setpoint Step
0 = -0.5ºC; 1 = +0.5ºC
82
2 Bytes
I
C - - W -
DPT_Value_Tempd
-670760.00 -
670760.00
[T1] Setpoint Offset
Float Offset Value
83
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 -
670760.00
[T1] Setpoint Status
Current Setpoint
84
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 -
670760.00
[T1] Basic Setpoint Status
Current Basic Setpoint
85
2 Bytes
O
C T R - -
DPT_Value_Tempd
-670760.00 -
670760.00
[T1] Setpoint Offset Status
Current Setpoint Offset
86
1 Bit
I
C - - W -
DPT_Reset
0/1
[T1] Setpoint Reset
Reset Setpoint to Default
1 Bit
I
C - - W -
DPT_Reset
0/1
[T1] Offset Reset
Reset offset
87
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
[T1] Mode
0 = Cool; 1 = Heat