background image

© Zennio Avance y Tecnología S.L.                        Edition 5                             Further informatio

www.zennio.com

                            

 

Page 

2

/

2

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
INSTALLATION AND CONNECTION 

 

 

This KNX power supply must be exclusively installed in a 
35mm  DIN  rail  inside  a  distribution  box  or  an  electrical 
panel. 

 

Ensure  suitable  ventilation  to  prevent  the  range  of  the 
permissible temperatures from being exceeded. 

 

Main  power  must  be  connected  to  L,  N  and  ground 
terminals, in accordance with the schematic represented 
in figure 2. 

 

The  coil  integrated  bus  output  must  be  connected 
through a standard KNX connector. 

 

The  additional  output  connection  must  be  connected 
according to the polarity indicated on the housing. 

 
 
CONTROLS AND INDICATORS 

 

Power LED indicates the status of the device : 

 

 

LED ON (green): the device is working properly. 

 

LED OFF: input voltage failure.

 

 

 

LED blinking (green): KNX bus and/or additional output short-circuit.    

 
Overload LED indicates if the maximum current specified is exceeded:  
 

 

LED OFF: maximum current specified is not exceeded. 

 

LED blinking (red): switch off due to overload/shortcircuit in the KNX bus and/or the additional output*.  

 

LED ON (red): bus and/or additional output line overload*.  

 

*Reduce the load on the bus and/or the additional output lines until its total consumption does not exceed the 
maximum current specified.

 

 

Note:  To  reset  the  bus  power  supply,  the  Reset  button  should  be  pressed  (it  is  recommended  to  hold  it  for  at  least  5 
seconds to verify the reset of all the  devices  in  the line). The Reset LED will blink slightly in  red while the  Reset button  is 
pressed. 
Note 2: two power supply units may work in parallel as long as none of them shows overload. In such case, the position on 
the KNX bus should be modified until the error disappears. 

 

 

 

Figure 2

: ZPS320HIC230 installation and connection 

220-240VAC 

50/60Hz 

 

EXTERNAL POWER SUPPLY SPECIFICATIONS AND CONNECTIONS

 

CONCEPT 

DESCRIPTION 

Power supply 
protection fuse  

Voltage 

250V 

Current 

4A 

Response type 

F (Fast acting) 

Connection method 

Screw terminal block 

Cable cross-section  

0.5mm² to 4mm² (26-10AWG) 

 

ADDITIONAL OUTPUT SPECIFICATIONS AND CONNECTIONS

 

CONCEPT 

DESCRIPTION 

Connection method 

Screw terminal block 

Cable cross-section  

0.5mm² to 4mm² (26-10AWG) 

 

SAFETY INSTRUCTIONS 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 The  facility  must  be  equipped  with  a  device  that  ensures  the  omnipolar  sectioning.  Installation  of  a  10A  mini-circuit-breaker  is 

recommended. To prevent accidents, it must remain open in case of manipulation of the device. 

 The device has a short-circuit protection fuse that, in case of activation, should only be rearmed or replaced by the Zennio technical 

service.  

 This device contains a security short-circuit proof transformer. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water and do not cover it with clothes, paper or any other material while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at 

http://zennio.com/weee-regulation. 

Removing Power Supply from DIN rail:

 

Attaching Power Supply to DIN rail: 

 