ZPS160MPA 

160 mA Power Supply 
ZN1PS-160MPA   

 

 

 

 

 

 

 

              

Technical Documentation 

 

© Zennio Avance y Tecnología S.L.                        Edition 4                             Further information 

www.zennio.com

                                   

Page 

2/2

 

 

     
  
 
 

GENERAL SYSTEM SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Device type 

Electric operating control device 

External power supply 

Voltage 

230 VAC, 50/60 Hz 

Consumption 

Max. 100mA  

KNX output 

Voltage 

29 VDC SELV  

Output (I

BUS

Max. 160mA  

Additional output 

Voltage 

29 VDC SELV 

Output (I

AUX

I

AUX 

+ I

BUS 

≤ 250mA

 

Operation temperature 

from -5ºC to +45ºC 

Storage temperature 

from -20ºC to +55ºC 

Operation humidity 

from 30 to 85% RH (no condensation) 

Storage humidity  

from 30 to 85% RH (no condensation) 

Complementary characteristics 

Class B 

Protection class 

Class I 

Operation type 

Continuous operation 

Device Action type 

Type 1 

Electrical stress period 

Long 

Installation 

Independent to be mounted inside distribution boxes or electrical 
panels. 

Minimum clearances 

--- 

Power failure back-up time 

200ms 

Max current before overload 

350mA 

Protection fuse  

Voltage 

250V AC ~ 50 Hz 

Current 

2.5 A 

Response 

Type F (fast response) 

Connection type 

Three screw terminals clamp 

Cable section 

from 0.5mm² to 2.5mm²   

Cable type 

Flexible cable with crimping terminals or rigid cable without 
terminals 

Operation indicator 

Green LED ON implies a correct bus voltage 

Weight 

200g 

PCB CTI index 

175V 

Housing material 

PC+ABS FR V0 Halogen free 

SAFETY INSTRUCTIONS 

 

Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country. 

 

Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the 

entire KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the 
wires of other accessories, in case of being installed. 

 

The  facility must  be  equipped  with  a  device  that  ensures  the  omnipolar  sectioning.  Installation of  a  10A mini-circuit-breaker  is 

recommended. To prevent accidents, it must remain open in case of manipulation of the device. 

 

The  device  has  a  short-circuit  protection  fuse  that,  in  case  of  activation,  should  only  be  rearmed  or  replaced  by  the  Zennio 

technical service.  

 

Once the device is installed (in the panel or box), it must not be accessible from outside. 

 

Keep the device away from water and do not cover it with clothes, paper or any other material while in use. 

 

The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions 

at http://zennio.com/weee-regulation. 