Firmware Update – Z41

 

http://www.zennio.com

 

 

            

Technical Support:

 

http://support.zennio.com 

 

2.2

 

TROUBLESHOOTING 

Event

 

Possible cause(s)

 

Solution

 

The update process 

does not start after 

connecting the USB 

memory

 

The 

.pak

 file has been renamed. 

Change the file name back to 

z41_update.pak

 for Z41, 

z41_pro_update.pak 

for Z41 

Pro or 

z41_lite_update.pak 

for Z41 Lite. 

The 

.pak

 file has not been saved 

into the root directory of the USB 

memory drive. 

Move the file to the root folder 

of the USB memory drive, 

e.g., 

X:\

The USB drive is not supported 

(non-flash memory, external hard 

drive, etc.). 

Use a flash memory drive or 

try with another. 

The file system in the USB 

memory is not 

FAT32

Format the USB memory to 

the FAT32 file system. 

More than one partition co-exist in 

the USB drive and the 

.pak 

file 

has not been found on the first 

partition detected by Z41 / Z41 

Pro / Z41 Lite. 

Define only one partition in the 

USB memory and save the 

.pak

 file to the root directory of 

that partition. 

The 

.pak

 file and the already 

loaded firmware on Z41 / Z41 Pro 

/ Z41 Lite have the same version. 

Obtain a more recent / 

different version of the 

.pak 

file, if available. 

The firmware update feature 

through the USB port has been 

disabled in ETS. 

Enable in ETS the update 

function via USB (making use 

of the particular application 

program version that is 

currently loaded on the 

device; see section 3.1.1) and 

download the parameters 

again. 

Summary of Contents for Z41

Page 1: ...Z41 Z41 Lite Z41 Pro Firmware Update via the USB Ethernet interfaces DOCUMENTATION Document version e www zennio com...

Page 2: ...c Important note about bus power failures within the first two minutes after a firmware update Self reconnection to network server with no need of a reboot 9 Possibility of enabling disabling the fir...

Page 3: ...rt http support zennio com 3 CONTENTS Document Updates 2 Contents 3 1 Introduction 4 2 Update via USB 5 2 1 Step by Step Process 5 2 2 Troubleshooting 7 3 Update via Ethernet 9 3 1 Step by Step Proces...

Page 4: ...work from a PC running the Windows operating system by means of the Ethernet adapter see the Z41 user manual bundled with the original packaging of the device This option is only available for Z41 and...

Page 5: ...r to section 3 1 1 and to the user manual of Z41 Z41 Pro or Z41 Lite for further detail These are the steps 1 Download from http www zennio com the ZIP file with the firmware corresponding to the desi...

Page 6: ...ne whether its version differs from that already installed if any If both versions are the same no update process will take place Important any firmware version newer or not can be downloaded to Z41 Z...

Page 7: ...ve or try with another The file system in the USB memory is not FAT32 Format the USB memory to the FAT32 file system More than one partition co exist in the USB drive and the pak file has not been fou...

Page 8: ...the application program version that corresponds to the firmware version or install a firmware that matches the current application program The update process was interrupted bus power failure unexpe...

Page 9: ...implemented for example in the network router that dynamically and automatically assigns IP addresses to any new devices joining the network Versions 1 x and 2 x of the Z41 application program only tr...

Page 10: ...where X may depend on the downloaded version 4 The installer will copy the required files to the PC and will add to the Start menu a direct access to the Z41 Update tool Note the PC must have the JAV...

Page 11: ...the Z41 or Z41 Pro user manuals and the individual address it was assigned in the KNX topology On the other hand In case of multiple network interfaces installed on the PC button will let the user ac...

Page 12: ...is currently in working mode Blue bar the device is in the Update mode the Status page is shown on the screen instead of the user interface Important any firmware version newer or not can be downloade...

Page 13: ...box is active 12 During the process the device being updated will show a progress bar At the end of the update the bar will disappear and the device will boot normally unless the application program c...

Page 14: ...if a new password is set by means of an additional parameter download from ETS important it is necessary to import into ETS the same version of the application program that may be running on the devic...

Page 15: ...Z41 Update tool does not find the device after performing a device search Z41 or the PC are not connected to a wired Ethernet network Connect the PC and Z41 to the wired Ethernet network Z41 is not be...

Page 16: ...ogram downloaded via ETS Download from ETS the application program version that corresponds to the firmware version or install a firmware that matches the current application program An old version of...

Page 17: ...d us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 Fax 34 925 337 310 www zennio com inf...

Reviews: